To avoid electric shock, do not touch the input signal terminal during power voltage application.
When connecting the input signal terminals of two or more GT3A timers to the same contact or transistor, the input terminals of the same number should be con-
nected. (Connect Terminals No.2 in common.)
[Incorrect]
GT3 Series
Input
Timer
Contact or Transistor
Input
Terminal
2
10
Power
Input
Terminal
2
10
In a transistor circuit for controlling input signals, with its primary and secondary power circuits isolated, do not ground the secondary circuit.
GT3 Series
Timer
Input
Terminal
Circuit
Insulating Transformer
Connect the input signal terminals of the GT3A timers to Terminal No.2 only. Never apply voltage to other terminals; otherwise, the internal circuit may be damaged.
R
Y
5, 6, and 7
Input Terminal
2
10
Power
Input signal lines must be made as short as possible and installed away from power cables and power lines. Use shielded wires or a separate conduit for