ATTENTION
Please read the following instructions carefully to ensure that mounting operation will be carried out correctly. These instructions
should be properly preserved for future reference.
CAUTION
1. The product must be installed by qualified technicians. The power supply must be cut before installation.
2. The installation wiring must be 2 x 1.0 mm² at least and wired in accordance with the latest IEE electrical regulations or the national requirements.
3. Cut the power supply before replacing battery.
4. Do not touch the electronic circuit and its components.
5. When fixture is unable to maintain the 1 hour duration under battery operation, then the battery must be replaced.
6. Contact an authorised technical service center for the replacement of the battery and use only original manufacturer spare parts for any
other repairs.
7. Code for identification of battery production date: ex.07/2020 --- year 2020, month 07.
8. Do not touch the LEDs while installing or maintaining.
9. The LED light source of the lamp cannot be replaced. The complete product must be replaced if the light source is defect.
10. The charge of the battery will decrease by self-discharge if not connected to mains supply. Prolonged periods without voltage can damage the
battery. Battery warranty claims, as a result of such abuse, are specifically EXCLUDED from warranty terms.
11. On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during construction. As a result, any unit on these
circuits, will have their batteries discharged or 'cycled' . Excessive battery cycling will reduce through-life performance and may lead to premature
battery failure. Battery warranty claims, as a result of such abuse, are specifically EXCLUDED from warranty terms.

TECHNICAL DATA

Supply voltage: AC 220-240V 50/60Hz
Light source: LED SMD2835
Battery: LiFePO
3.2V Duration: 1 hour
4
Operating temperature: 0°C - +50°C (Sensor version: upto max. +40°C)
Electrical safety class: Class II

TECHNICAL INFORMATION

Article no.
Voltage
White version
40009372
220-240V 50/60Hz
40009373
220-240V 50/60Hz
Black version
40009377
220-240V 50/60Hz
40009378
220-240V 50/60Hz
MICROWAVE SENSOR - DESCRIPTION
Detection zone max. (d x h): 12m x 6m
Detection sensitivity: 50% or 100%, adjustable
Hold time: 5sec - 10min, adjustable
Daylight on: 5 - 50Lux, adjustable or disabled
Daylight off: 25 - 150Lux, adjustable or disabled
Stand-by period (low light level): 0 sec - +∞ min, adjustable
Stand-by dim level: 10% or 25%, adjustable
Ceiling mounting height: 6m max.
Motion detection (threshold): 0.3 ~ 3m/s
Detection angle: 150° (wall installation),
360° (ceiling installation)
LED type
Power
Light output
SMD2835
16W
850Lm / 1190Lm / 1700Lm
SMD2835
17.5W
850Lm / 1190Lm / 1700Lm
SMD2835
16W
750Lm / 1050Lm / 1500Lm
SMD2835
17.5W
750Lm / 1050Lm / 1500Lm
Wall mounting detection area (m)
Suggested installation height: 2m
www.prolumia.com
LED Prodisc III
Light output
emergency mode
270Lm
270Lm
235Lm
235Lm
Walking speed: 0.3m/s
MW sensor
-
Yes
-
Yes
Ceiling mounting detection area (m)
Suggested installation height: 3m
Walking speed: 0.3m/s