Specifications; Technical Specifications - Emerson Rosemount 975 Series Reference Manual

Flame detectors
Hide thumbs Also See for Rosemount 975 Series:
Table of Contents

Advertisement

Reference Manual
00809-1400-4975
7

Specifications

7.1

Technical specifications

Spectral response
Rosemount 975MR
Rosemount 975HR
Rosemount 975UF
Rosemount 975UR
Detection range per fuel (ft/m)
Note
The ranges shown are at highest sensitivity setting for 1ft
Table 7-1: Rosemount 975 Models
Fuel
Gasoline
N-Heptane
Diesel fuel
Kerosene
Alcohol 95%
IPA
Methanol
Methane
LPG
Polypropylene
Paper
Hydrogen
Magnesium
alloy
Gun powder
Fireworks
Cooking oil
Mineral oil:
20w50
Rosemount 975
Rosemount
975MR
300/90
300/90
210/63
210/63
185/55
185/55
185/55
207/63
207/63
160/49
112/34
N/A
N/A
(1)
197/60
33/10
207/63
207/63
Four IR bands between 4μm and 5μm
Four IR bands between 2μm and 5μm
UV: 0.185 - 0.260 μm
IR: 2.5-3.0 μm
UV: 0.185 - 0.260 μm
IR: 4.3 – 4.8μm
2
Rosemount
Rosemount
975HR
975UF
93/28
93/28
70/21
70/21
57/17
70/21
57/17
60/18
60/18
60/18
33/10
164/50
70/21
33/10
66/20
10/3
70/21
70/21
Specifications
June 2021
2
(0.1m
) pan fire.
Rosemount
975UR
N/A
92/28
25