Diesel Tank Withcontainmentbasin Andventconnection - Grundfos Hydro 50-250/263 YJS ASD-U3-B Installation And Operating Instructions Manual

Firefighting systems
Table of Contents

Advertisement

4.4 Diesel tank with containment basin
and vent connection
CAUTION
Toxic material
Minor or moderate personal injury
The fuel vent pipe must be installed properly and
make sure that all the parts are firmly supported and
all the connections are perfectly sealed in order to
avoid concentration of fuel vapours in the technical
room.
Periodically check the integrity of the vent pipe.
Smoking and live flames are prohibited when refuelling.
During refuelling, use adequate refuelling tools and
avoid lifting excessive loads, which can cause falls or
musculoskeletal problems.
B
A
Pos.
A
B
Fuel tank
Description
Sight glass
Connection for vent pipe
Use appropriate lifting techniques and do not bend the
waist.
Only use suitable fuel (refer to the engine manual). The
unsuitable fuel can ignite flames and/or cause serious
damage to the fire pump set or even to the system.
The diesel pump are equipped with a fuel tank equipped with a
containment basin. The capacity of the containment basin equals to
the capacity of the tank itself.
The basin prevents diesel from leaking if the tank breaks or leaks.
As seen in the figure below, there is a sight glass (pos. A) on the
side of the basin for a visual check of the tank. The diesel tank is
also supplied with a connection for the vent pipe (pos. B).