Installation Requirements; Installation Room - Grundfos Hydro 50-250/263 YJS ASD-U3-B Installation And Operating Instructions Manual

Firefighting systems
Table of Contents

Advertisement

Lifting the electric unit.
Lifting the diesel unit.
See also the installation and operating instructions for the diesel
engine.
10

4. Installation requirements

Refer to the system design for the information of the room
installation, specifically for the construction works, ventilation, air
exchange, power supply system and the evacuation
of the exhaust gases of the diesel engine. The installation must be
carried out timely by specialists appointed by the client in
compliance with relevant regulations and provisions.
The main criteria for installing firefighting pump sets are described
in the EN 12845 standard. You also need to refer to the local
regulations if applicable.

4.1 Installation room

Leave necessary space in the installation room during
design for installing, using, maintaining and disassembling
the fire pump.
The design of the installation room must be carried out by
a qualified designer appointed by the client in accordance
with local regulations.
Before installation, make sure the following items are fulfilled:
The installation room dimensions are adequate for the pump set
to be installed.
The room has proper air circulation.
The product must be installed in an access-
controlled area. Make sure that only qualified persons
have access to this area.
If the site is left unattended before the installation is
completed, all openings must be covered to
prevent foreign objects from entering, such as children,
animals and stones.
Use unbreakable covers that cannot be removed without
tools.
The Hydro EN pump sets must be installed in a weatherproof room
protected from freezing. The room must be well ventilated to
ensure proper cooling of the electric motors and diesel engines.
Make sure that the operating conditions do not exceed those stated
in Technical data.
Pay attention to the correct evacuation of diesel engine
exhaust gases. For this purpose, adequate ventilation ducts must
be installed.
The installation room of the pump set must be properly sized
according to regulations in force and good practices. You must take
the following into account:
the overall dimensions of the pump set
easy access to the parts of the pump set for commissioning,
routine checks and maintenance
the need to have an adequate exchange of air in the room to
ensure proper cooling of the machines.