VS8510/VS8520 MILLIVOLT COMBINATION GAS CONTROL
STANDING PILOT MILLIVOLT VALVE
ON POSITION (VALVES OPEN)
ON
OFF
SUPPLY ORIFICE
INTLET
SAFETY VALVE
3. If necessary, adjust the pressure regulator to match the
appliance rating. See Table 3 for factory-set nominal
outlet pressure and adjustment range.
a.
Remove pressure regulator adjustment cap screw.
b.
Using a screwdriver, turn inner adjustment screw
clockwise to increase or counterclockwise to
decrease gas pressure to burner.
c.
Always replace cap screw and tighten firmly to
prevent gas leakage.
68-0203
SERVO
VALVE
PILOTSTAT
KNOB
POWER
UNIT
Fig. 11. Safety and main valve are open.
VENT
MILLIVOLT
OPERATOR
MAIN VALVE
OUTLET
PILOT TUBE
INLET GAS
OUTLET GAS
WORKING GAS
4. If desired outlet pressure or flow rate cannot be
achieved by adjusting the gas control, check gas control
inlet pressure using a manometer at the gas control
inlet pressure tap. If inlet pressure is in the normal
range (see Table 3), replace gas control. Otherwise,
take the necessary steps to provide proper gas
pressure on the control.
10
SERVO
REGULATOR
Q313
THERMOPILE
ELECTRODE
MAIN BURNER
Q377 PILOT
BURNER
CONNECT
THERMOPILE
LEADWIRES TO
GAS CONTROL
CONNECT ELECTRODE
LEADWIRE TO PIEZO
IGNITER
M15095