Distance between cooktop and ventilation hood (S)

Provided a larger distance is not given by the manufacturer of the cooktop,
follow the minimum safety distances between a cooktop and the bottom of the
hood.
Please also observe the information contained in the "IMPORTANT SAFETY
INSTRUCTIONS" section.
Cooking appliance
Electric Cooktops
Electric Barbeques and Fryers
Multiburner Gas Cooktops
≤ 43,000 BTU/hr (12.6 kW),
no burner > 15,000 BTU/hr (4.5 kW).
Multiburner Gas Cooktops
≤ 73,800 BTU/hr (21.6 kW),
no burner > 16,500 BTU/hr (4.8 kW)
Multiburner Gas Cooktops
> 73,800 BTU/hr (21.6 kW),
or one of the burners > 16,500 BTU/hr (4.8 kW)
Single Burner Gas Cooktops
≤ 20,500 BTU/hr (6 kW)
Single Burner Gas Cooktops
> 20,500 BTU/hr (6 kW)
≤ 27,600 BTU/hr (8.1 kW)
Single Burner Gas Cooktops
> 27,600 BTU/hr (8.1 kW)
Installation
Minimum distance S
Miele
appliance
24" (610 mm)
26" (660 mm)
26" (660 mm)
30" (760 mm)
Not possible
26" (660 mm)
30" (760 mm)
Not possible
Non-Miele
appliance
30" (760 mm)
30" (760 mm)