Trumeter APM Quick Start Manual
Hide thumbs Also See for APM:

Advertisement

Quick Links

APM
POWER METER
Before installation, read the Safety
Warnings overleaf.
CAUTION: Risk of Danger
Read complete instructions prior to installation and
operation of the unit
CAUTION: Risk of electric shock
Intended Use: The APM has been specifically designed for engineers requiring an effective way to monitor and
display data. The APM accepts a range of electrical inputs (depending on the model) and displays the data on its
integrated multi-format display. The APM has been designed for industrial use only, by installation into electrical
cabinets or display panels.
Voltage (V)
Current (I)
Power (W/VA/VAr)
Frequency
Voltage (V)
Current (I)
Frequency
THD
Power (W/VA/Var)
1.800.561.8187
Operating Specification
Measurement Range
Measurement Accuracy of full scale
www.
.com
L-L: 10 - 600VAC
L-N: 10 -300VAC
0–5A (CT only)
0-999,999MW
Dependant on CT ratio
45 – 65 Hz
1%
1%
1%
5%
1%
information@itm.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the APM and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Trumeter APM

  • Page 1 Intended Use: The APM has been specifically designed for engineers requiring an effective way to monitor and display data. The APM accepts a range of electrical inputs (depending on the model) and displays the data on its integrated multi-format display. The APM has been designed for industrial use only, by installation into electrical cabinets or display panels.
  • Page 2: Modbus Connections

    Wiring Diagrams MODBUS CONNECTIONS MODBUS AND OUTPUTS CURRENT MEASUREMENT VOLT AGE MEASUREMENT DIGITAL OUTPUT CONNECTIONS MODBUS AND OUTPUTS CURRENT MEASUREMENT VOLTAGE MEASUREMENT 1.800.561.8187 information@itm.com www. .com...
  • Page 3 Wiring Diagrams ANALOG OUTPUT CONNECTIONS 4-20mA +88.8 MODBUS AND OUTPUTS CURRENT MEASUREMENT VOLTAGE MEASUREMENT SINGLE PHASE POWER METER CONNECTIONS - LINE POWER MODBUS AND OUTPUTS CURRENT MEASUREMENT VOLTAGE MEASUREMENT NOTE: DO NOT CONNECT CT SECONDARYS TO EARTH. CT’S EARTHED THROUGH N TERMINAL 1.800.561.8187 information@itm.com www.
  • Page 4 Wiring Diagrams SINGLE PHASE POWER METER CONNECTIONS - LOCAL POWER FUSE MODBUS AND OUTPUTS CURRENT MEASUREMENT VOLTAGE MEASUREMENT NOTE: DO NOT CONNECT CT SECONDARYS TO EARTH. CT’S EARTHED THROUGH N TERMINAL SPLIT PHASE POWER METER CONNECTIONS - LINE POWER MODBUS AND OUTPUTS CURRENT MEASUREMENT VOLT AGE MEASUREMENT NOTE: DO NOT CONNECT CT SECONDARYS TO EARTH.
  • Page 5 Wiring Diagrams SPLIT PHASE POWER METER CONNECTIONS - LOCAL POWER FUSE MODBUS AND OUTPUTS CURRENT MEASUREMENT VOLTAGE MEASUREMENT NOTE: DO NOT CONNECT CT SECONDARYS TO EARTH. CT’S EARTHED THROUGH N TERMINAL THREE PHASE AND NEUTRAL POWER METER CONNECTIONS - LINE POWER MODBUS AND OUTPUTS CURRENT MEASUREMENT VOLTAGE MEASUREMENT...
  • Page 6 Wiring Diagrams THREE PHASE (NO NEUTRAL) POWER METER CONNECTIONS - LOCAL POWER FUSE MODBUS AND OUTPUTS CURRENT MEASUREMENT VOLTAGE MEASUREMENT EARTH NOTE: DO NOT CONNECT CT SECONDARYS TO EARTH. CT’S EARTHED THROUGH N TERMINAL THREE PHASE POWER METER CONNECTIONS with PT AND CT - LOCAL POWER FUSE MODBUS AND OUTPUTS...
  • Page 7: Safety Warnings

    Safety Warnings WARNING: INSTALLATION AND MAINTENANCE MUST BE CARRIED OUT BY SUITABLY QUALIFIED AND COMPETENT PERSONEL ONLY. HAZARDOUS VOLTAGES MAY BE PRESENT ON THE CONNECTION TERMINALS. INSTALLATION • Install this product in accordance with local regulations, codes and instructions. • An external fuse must be fitted in-line with the PSU. Recommended fuse: 0.5A/300V with a breaking capacity of 35A or greater.
  • Page 8: Specification

    Specification VALUE Environment Temperature - operating –10 to +50°C Temperature - storage –40 to +70°C Altitude 2000 metres Relative Humidity (non-condensing) - Continuous 0 – 85 % Relative Humidity (non-condensing) - Intermittent 0 – 95 % Overvoltage category (IEC664) Pollution Degree (IEC664) IP rating (from the front) IP65 NEMA Rating (from the front)
  • Page 9: Control Outputs

    Control Outputs Isolation Modbus Current Control Input Inputs Analog Output Voltage Input Power Supply Isolation barriers: Galvanic Isolation Barrier Size Size of the cutout in the panel: 68 x 68mm (2.68in) +0.7 -0mm Front Panel Buttons Change Parameter: Auto Scroll Parameters: Press to automatically switch Press to move between parameters parameters every 3 seconds...

Table of Contents