INSTRUCTION
EN
CTR25
i
Read this instruction before installation
and wiring of the product
Consult documentation in all cases where this symbol
is used, in order to find out the nature of the potential
hazards and any actions to be taken
Triac controller for proportional control
of electric heating
CTR25 is a proportional controller for electric heating with automatic
voltage adaption. CTR25 pulses the whole load On - Off. The ratio
between On-time and Off-time is varied 0 - 100% to suit the prevailing
heat demand. The current is always switched at zero phase angle to
prevent RFI.
CTR25 can control both symmetrical Y-connected 3-phase heaters
and symmetrical or asymmetrical Delta-connected heaters.
CTR25 is only intended for electric heating control. The control
principle makes it unsuitable for motor- or lighting control.
CTR25 is intended for DIN-rail mounting.
Installation
Mount CTR25 on a DIN-rail in a cabinet or other enclosure.
Mount CTR25 vertically with the text right side up.
Protection class:
IP20.
Ambien temperature:
0 - 40°C
N.B. CTR25 emits approx. 45W of heat at full output which must be
dissipated.
Wiring
Supply voltage
Terminals L1in, L2in and L3in.
Supply voltage:
210-255 or 380-415V AC
3 phase, 50 - 60 Hz with automatic voltage adaption.
Maximum current 25A/phase.
N.B. The supply voltage to CTR25 should be wired via an all-pole switch
with a minimum contact gap of 3mm.
N.B. CTR25 must be earthed.
1
2 3 4 5 6 7 8 9
L1 L2 L3 L3 L2 L1
1 1
3
Figure 1: Wiring of supply voltage and load
Load
Terminals L1out, L2out and L3out.
Resistive 3-phase heater without neutral.
Maximum load:
3300W/phase at 230V phase - phase voltage (25A).
5750W/phase at 400V phase - phase voltage (25A).
Minimum load:
530W/phase at 230V phase - phase voltage (4A).
920W/phase at 400V phase - phase voltage (4A).
Main sensor and external setpoint (figs 2-5)
Terminals 1 and 4. Low voltage. Not polarity sensitive.
N.B. Terminals 2 and 3 are internally connected and are used to simplify
wiring when using external setpoint.
N.B. Choice of internal or external setpoint is made using switch 1.
CTR25
1 2
3 4
SA-NTC15-01
1
2
Figure 2: Wiring of room sensor SA-NTC15-01 when
using internal setpoint
1 2
3 4
1
3
SAP-NTC15-01-3
Figure 3: Wiring of room sensor SAP-NTC15-01-3 used as
external setpoint and sensor
1 2
3 4
STCC-NTC15-02
Figure 4: Wiring of floor or duct sensor when using
internal setpoint
1 2
3 4
STCC-NTC15-02
2
3
SAP-NTC15-01-3
Figure 5: Wiring of external separate sensor when using SAP-
NTC15-01-3 as external setpoint
1

Advertisement

loading

Summary of Contents for industrie technik CTR25

  • Page 1 Mount CTR25 vertically with the text right side up. Protection class: IP20. Ambien temperature: 0 - 40°C N.B. CTR25 emits approx. 45W of heat at full output which must be Figure 2: Wiring of room sensor SA-NTC15-01 when dissipated. using internal setpoint Wiring Supply voltage Terminals L1in, L2in and L3in.
  • Page 2: Control Principle

    Switch the voltage on. CTR25 can also be run against a 0 - 10V DC control signal from another Choice of function is made using switches 2 and 3. Choice of limiting CTR25 should give full uninterrupted power and the LED should controller.
  • Page 3: Installazione

    Temperatura ambiente: 0...40 °C NTC15-01 quando si utilizza il setpoint interno N.B.: Il CTR25 dissipa a pieno carico ca. 45 W di calore, i quali Figura 6: Cablaggio del sensore di limitazione devono essere dissipati adeguatamente. N.B.: Deve essere utilizzato l’ STCC-NTC15-02 come sensore di Cablaggio limitazione.
  • Page 4 Giù = utilizzato setpoint esterno. corretta. Su = utilizzato setpoint interno. Se fino ad ora è tutto in ordine, il CTR25 e il sensore/setpoint Giù = limite minimo non attivo. Misurare la resistenza fra i morsetti L1out - L2out, L1out - L3out e sono a posto.
  • Page 5: Einbau

    Montieren Sie den CTR25 auf einer DIN-Hutschiene in einem Die Funktionswahl wird mittels den Schaltern 2 und 3 gemacht. Schaltschrank oder Ähnlichem. Die Minimal- oder Maximal-temperatur wird mittels den Potis einges- Montieren Sie den CTR25 vertikal sodaß der Text zu lesen ist. tellt. Schutzklasse: IP20.
  • Page 6 Externes Regelsignal Der CTR25 sollte voll, ununterbrochen durchschalten und die LED www.industrietechnik.it - info@industrietechnik.it Der CTR25 kann auch mittels 0 - 10V DC Signal von einem anderen sollte leuchten. Testen Sie mit einem Zangenamperemeter ob der Regler gesteuert werden. Strom auch durch die Last fließt.
  • Page 7: Installation

    NOTE: le sélecteur de fonction 1 permet de choisir une consigne interne Le CTR25 est monté sur un rail DIN. ou externe. Installation Monter le CTR25 sur un rail DIN dans une armoire ou un autre STCC-NTC15-02 boîtier. SA-NTC15-01 Monter le CTR25 à la verticale avec le texte à l’endroit.
  • Page 8 Éteindre la tension d’alimentation et court-circuiter les entrées 1 et 4 de la sonde. Remettre la tension d’alimentation en marche. Le CTR25 ne doit pas fournir de puissance du tout. Le voyant doit être éteint. Contrôler avec une pince ampèremétrique que le ré-...