CMF
CMF10 is a pre-programmed controller that can be used
for control of temperature, CO
in air handling and heating applications. It is a stand-alone
controller for simpler applications. CMF is extremely easy
to install, commission and control.
CMF uses a display with an encoder knob, making
its built-in menu system very easy to use. Settings
are entered by turning the encoder knob to a desired
parameter/value. A value is then approved by pressing the
knob.
Models
The CMF series comprises two different types, CMF5U
and CMF10.
CMF5U has 5 in-/outputs and CMF10 has 10 in-/outputs.
CMF10 is available in two versions:
• CMF10 with 24 V AC supply voltage
• CMF10-230 with 230 V AC supply voltage
CMF has been developed according to our Ready-Steady-
Go concept, which simplifies every step from installation to
management.
CMF10
, pressure, and humidity
2
CMF10
Pre-programmed, configurable controller for
simple applications
The CMF10 range of controllers can be set to handle
everything from temperature or humidity control to
control of CO
or pressure. They are intended for DIN-
2
rail mounting.
• Pre-loaded with several application modes
• 24 V or 230 V AC supply voltage
• Week-based clock / calendar function
Applications CMF10 and CMF10-230
CMF10 is pre-programmed with a choice of five different
control modes:
1. Supply air control
2. Supply air control with outdoor compensation
3. Cascaded room / extract air temperature control
4. Radiator circuit control
5. Domestic hot water control
Inputs and outputs
CMF10 has
• 2 analogue inputs, PT1000
• 1 SPI input for an external setpoint device
• 1 universal input, PT1000 or digital
• 2 digital inputs
• 3 digital outputs
• 2 analogue outputs, 0...10 V DC
Internal clock
CMF10 has a built-in week-based real-time clock with a
number of different scheduler alternatives.
Easy to install
CMF is suitable for DIN-rail or cabinet mounting. Since
the terminals are detachable all connections can be made
before CMF is installed.
revision
10 2015

Advertisement

loading

Summary of Contents for industrie technik CMF10

  • Page 1 • Simple configuration via the backlit display • 24 V or 230 V AC supply voltage • Input for an external setpoint device • Week-based clock / calendar function Applications CMF10 and CMF10-230 CMF10 is a pre-programmed controller that can be used CMF10 is pre-programmed with a choice of five different for control of temperature, CO , pressure, and humidity control modes: in air handling and heating applications.
  • Page 2: Display Handling

    CMF10 Display handling Display - Base level This is an example of the display when in Base level view All setting and configuration is performed using the mode. It is normally shown when there is no operator display and encoder knob on the front of the controller.
  • Page 3: Function Overview

    CMF10 Configuration All configuration menus lie in the 10-seconds level. This level is accessed from the Base Display by pressing and holding the encoder button for 10 seconds. There are numerous configuration menus covering all available options and combinations. In some cases, making a certain choice in one menu will mean that you will only see certain other menus.
  • Page 4: Application Examples

    CMF10 Application examples CMF10 can be configured to any one of the following control modes. The three modes on this page have much in common and will therefore be treated in a single section. Supply air control Cascade connected room/extract air temperature...
  • Page 5 CMF10 Radiator circuit control with outdoor curve Domestic hot water control The water temperature setpoint is changed according The water temperature is kept constant by controlling the to the outdoor temperature. A single PI control loop is output signal on AO1. A single PID control loop is used.
  • Page 6: Technical Data

    CMF10 Technical data Supply voltage CMF10: 24 V AC ±15%, 50...60 Hz CMF10-230: 230 V AC +10%, -15%, 50...60 Hz Internal consumption 4 VA Ambient temperature 0...50°C Storage temperature -20...+70°C Ambient humidity Max. 90 % RH Display Numeric/graphic, backlit Protection class...
  • Page 7: Product Documentation

    CMF10 Wiring CMF10-230V CMF10 Terminal Designation Operation Terminal Designation Operation 24 V AC 230 V AC CMF10 only CMF10-230 only Terminal Designation Operation Common Change-over relay, 5A Reference for DO1 and DO2 Digital output Digital output AGND Reference for AO1 and AO2 0...10 V DC output...