Filling The Vessels And Control Unit; Bleeding The Pumps - Reflex variomat 1 Assembly, Operating, And Maintenance Instructions

Pressure-maintaining station
Table of Contents

Advertisement

reflex 'variomat'
Initial start-up

Filling the vessels and control unit

The following information applies to all 'variomat' systems with VG basic vessel and/or
one or more VF secondary vessels (expansion vessels).
Important: The VG and VF vessels must be empty for setting of the 'variomat'
controller. Auto-zeroing of the level gauge must therefore be performed before
the vessels are filled (see start routine/customer menu).
1.
Filling with a hose using the filling and draining tap (17) on the vessel.
This variant is recommended and useful if the automatic water make-up facility of the
'variomat' has not yet been connected on the water side.
To do this, connect a water hose from the water supply to the filling and draining tap
(17) on the vessel. Open the protected shut-offs between the control unit and the vessel
(factory setting: open).
0%
2.1 bar
Stop
30%
2.,1 bar
Stop
2.
Filling with the water make-up solenoid valve
18
Open the water make-up solenoid valve in manual mode and fill the vessel (→ p. 20).

Bleeding the pumps

Prerequisite: The VG basic vessel of the 'variomat' is filled (see abovementioned
point) and protected ball valves (21) are open (factory setting: open).
Loosen the bleed screw (9) of the pressure-maintaining pump and bleed the pump
until water containing no bubbles runs out. Tighten the bleed screw again and check
for watertightness. For 'variomat 2-2', repeat procedure for second pump.
It may be necessary to repeat this process several times if the delivery performance
of the pump/pumps remains poor.
Caution must be exercised at high temperatures!
Note the general safety instructions!
Switch on the controller (→ p. 16) and set it to "Stop"
operating mode. (This is used to show the water level in the
vessel.) The display should now be showing "0%".
Open the filling and draining tap (24) and fill the vessel:
– Heating system
– Cooling and air conditioning system
approx. 30%
approx. 50%
Example:
Bleed screws
'variomat 2-2/60'
24
stop
hand
12