Electrical connection

Electrical wiring and connection must be performed by a qualified electrician according to the applicable local
(electricity board) regulations and VDE regulations. The system must be de-energised before any work
is carried out on electrical components. Comprehensive electrical connection diagrams are enclosed with
these instructions and must be adhered to.
The following information applies only to standard systems and is largely restricted to the connections required
on site.
– Loosen the 2 recessed head screws on the control box (13).
– Open the cover.
– Pass all the cables to be installed through the cable conduit fitting.
Important: Use only cable conduit fittings suitable for the respective cable.
– Connect all cables (refer to the following and electrical circuit diagram).
– Note the connected loads on p. 29 for on-site fuse protection.
Overview of the wiring diagram on the circuit board - 'variomat 2'
I/O circuit board - single-pump system
Designation
Terminal
Supply
X0 / 1
(230 V)
X0 / 2
X0 / 3
Supply
X0 / 1
(400 V)
X0 / 2
X0 / 3
X0 / 4
X0 / 5
Make-up (4)
(230 V)
Dry-running
protection message
(fl oating)
Common message
(fl oating)
Level gauge
(pressure cell)
(8)
Contact water meter
(optional)
Pressure
transducer (4)
Pump 1 (2)
(230 V)
Signal
L
Wiring at the terminal block next to the fuses, pre-wired
N
with a shock-proof plug
PE
L1
L2
Wiring at the terminal block next to the contactors -
L3
wire 'variomat 2' on site
N
PE
4
Y1
5
N
Wire on site, optional
6
PE
13
14
Wire on site, optional
23
NC
24
COM
Wire on site, optional
25
NO
35
+18 V
36
GND
Is connected in the control box, put the plug on the
pressure cell on site and screw on tightly
37
AE
38
PE (screen)
43
+24 V DC
Wire on site, additionally connect the pins 7/8 on the
44
E1
jumper block J2 (see above figure)
39
+18 V
40
GND
Is connected
41
AE
42
PE (screen)
15
M1
16
N
Is connected
17
PE
reflex 'variomat'
I/O circuit board - dual-pump system
Remarks
Assembly
13
J2 7/8 (fourth from
left) occupied
→ Contact water
meter can be
evaluated

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents