Download Print this page

Pittway SYSTEM SENSOR SPECTRAlert SC2415W Installation And Maintenance Instructions

Ceiling mount series strobes, and horn/strobes

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
SpectrAlert Ceiling Mount Series Strobes,
and Horn/Strobes
For use with the following models:
Strobes:
24 volt: SC2415W, SC241575W, SC2430W, SC2475W, SC2495W, SC24115W, SC24177W
Horn/Strobes: 24 volt: PC2415W, PC241575W, PC2430W, PC2475W, PC2495W, PC24115W, PC24177W
Remove suffix "W" for red models.
Add suffix "P" for models with plain housing.
The Products to which this manual applies may be covered by one or more of the following U.S. Patent numbers: 5,914,665; 5,850,178; 5,598,139; 6,049,446; 6,057,778; D424465
Specifications
Mechanical
Input Terminals:
Overall Dimensions:
Operating Temperature:
Electrical
Voltage Range:
15 candela through 115 candela models
Strobes & Horn/Strobes:
(with MDL module):
177 candela models only
Strobes & Horn/Strobes:
(with MDL module):
Flash Rate:
Light Output:
Sound Output:
Listings:
Note: Strobes have a 16–33 Volt Operating Range Limit. Do not exceed the maximum number of 70 strobe lights when connecting the MDL Sync mod-
ule zone with a maximum line impedance of 4 Ohms per loop.
General Description
The SpectrAlert ceiling mount series notification appliances are designed to
meet the requirements of most agencies governing these devices, includ-
ing: NFPA, The National Fire Alarm Code, UL, FM, CSFM, MEA. Also,
check with your local Authority Having Jurisdiction for other codes or stan-
dards that may apply.
The SpectrAlert ceiling mount series can be installed in systems using 24-
volt panels having DC or full-wave rectified (FWR) power supplies. The
series can also be installed in systems requiring synchronization (module
MDL required) or systems that do not require synchronization (no module
required).
NOTICE: This manual shall be left with the owner/user of this equipment.
Fire Alarm System Considerations
Temporal and Non-Temporal Coded Signals:
The American National Standards Institute and the National Fire Alarm
Code require that all horns used for building evacuation installed after July
1, 1996, must produce Temporal Coded Signals.
Signals other than those used for evacuation purposes do not have to pro-
duce the Temporal Coded Signal. Temporal coding is accomplished by inter-
rupting a steady sound in the following manner:
1
1
1
/
Sec.
/
Sec.
/
Sec.
2
2
2
On
Off
On
Power Supply Considerations
Panels typically supply DC filtered voltage or FWR (full-wave rectified)
voltage. The system design engineer must calculate the number of units
used in a zone based on the type of panel supply. Be certain the sum of
D900-22-00
12 to 18 AWG (3.31 to 0.82 mm
6.8" diameter (173 mm)
32° F to 120° F (0° C to 49° C)
DC or Full-Wave Rectified
16 to 33 volts DC or Full Wave Rectified
17 to 33 volts DC or Full Wave Rectified
16 to 33 volts DC; 20 to 33 volts Full Wave Rectified
17 to 33 volts DC; 21 to 33 volts Full Wave Rectified
NOTE: Horn/Strobes units will operate on walk tests with on-time durations of 1 sec. or greater.
1 Flash Per Second
Models with 15 only in the model number are listed at 15 candela.
Models with 1575 are listed at 15 candela per UL 1971 but will provide 75 candela on axis (straight down).
Models with 30, 75, 95, 115, 177 are for that candela.
Sound output levels are established at Underwriters Laboratories in their reverberant room. Always use the sound out-
put specified as UL Reverberant Room when comparing products.
UL S5512 Strobe, UL S4011 (Combo)
1
1
1
/
Sec.
/
Sec.
1
/
Sec.
2
2
2
Off
On
Off
2
)
all the device currents do not exceed the current capability of the panel.
Calculations are based on using the device current found in the subsequent
charts and must be the current specified for the type of panel power sup-
ply used.
Wire Sizes
The designer must be sure that the last device on the circuit has sufficient
voltage to operate the device within its rated voltage. When calculating the
voltage available to the last device, it is necessary to consider the voltage
drop due to the resistance of the wire. The thicker the wire, the less the
voltage drop. Generally, for purposes of determining the wire size neces-
sary for the system, it is best to consider all of the devices as "lumped" on
the end of the supply circuit (simulates "worst case").
Typical wire size resistance:
18 AWG solid:
16 AWG solid:
14 AWG solid:
12 AWG solid:
Example: Assume you have 10 devices on a zone and each requires 50 mA
average and 2000 Ft. of 14 AWG wiring (total length=outgoing +return).
The voltage at the end of the loop is 0.050 amps per device x 10 devices x
3 ohms/1,000 ft. x 2000 ft =3 volts drop.
The same number of devices using 12 AWG wire will produce only 2 volts
drop. The same devices using 18 AWG wire will produce 8 volts drop.
Repeats
Consult your panel manufacturer's specifications, as well as SpectrAlert's
operating voltage range to determine acceptable voltage drop.
Note: If class "A" wiring is installed, the wire length may be up to 4 times
the single wire length in this calculation.
1
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Approximately 8 ohms/1,000 ft.
Approximately 5 ohms/1,000 ft.
Approximately 3 ohms/1,000 ft.
Approximately 2 ohms/1,000 ft.
A Division of Pittway
I56-1453-006R

Advertisement

loading
Need help?

Need help?

Do you have a question about the SYSTEM SENSOR SPECTRAlert SC2415W and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Pittway SYSTEM SENSOR SPECTRAlert SC2415W

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS SpectrAlert Ceiling Mount Series Strobes, A Division of Pittway and Horn/Strobes 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 For use with the following models: www.systemsensor.com Strobes: 24 volt: SC2415W, SC241575W, SC2430W, SC2475W, SC2495W, SC24115W, SC24177W Horn/Strobes: 24 volt: PC2415W, PC241575W, PC2430W, PC2475W, PC2495W, PC24115W, PC24177W Remove suffix “W”...
  • Page 2 Figure 1A: Current Draw Measurements (Average Mean Method) NOTE: The SC24177 and PC24177 strobes were only tested at the 20-33 Volt-FWR limits and 16-33 Volt DC limits, all other SC and PC strobes were only tested at the 16-33 Volt-FWR/DC limits. This does not include the 80% low end or 110% high end voltage limits. Ceiling Mount Horn/Strobe 15 cd: Ceiling Mount Strobe Only: Average Mean Current (mA)
  • Page 3 Figure 1C: Sound Pressure Measurements Figure 1D: Positioning for Maximum Brightness NOTE: For maximum brightness, Sound Output Guide Sound pressure unit must be mounted with dBA @10 ft./volts DC flash angles as shown. Temporal Low Volume Electromechanical 3000 Hz Interrupted High Volume Electromechanical 3000 Hz Interrupted Non-...
  • Page 4 Mounting Diagrams: Strobe or Horn/Strobe with universal mounting plate: Screw types used for mounting: 1. Mount adapter plate to back box with screws B. A = #8 plastite 2. Complete field wiring. B = 8-32 x 3/4 pan head 3. Secure unit to plate with screws A. Strobe or Horn/Strobe surface mount: 1.

This manual is also suitable for:

System sensor spectralert sc241575wSystem sensor spectralert sc2430wSystem sensor spectralert sc2475wSystem sensor spectralert sc2495wSystem sensor spectralert sc24115wSystem sensor spectralert sc24177w ... Show all