2.

DESCRIPTION

2.1.

Overview

The DAT 420 is a gas detector designed to detect the presence of toxic gases or oxygen deficien-
cy in ambient air. It operates using an electrochemical sensor whose measure is converted by the
transmitter into a 4-20 mA electrical signal which varies according to the gas/oxygen concentra-
tion. This signal is delivered to the control unit or to the Programmable Logic Controller (PLC)
through a 2-wire current loop.
The DAT 420 is suitable for:
Use in hazardous areas other than mines (ATEX group II - equipment category 2);
Use in zone 1 and 2 (gas) and 21 and 22 (dust) hazardous areas of explosive atmospheres;
Operating at temperature from -10 °C to +40 °C for T6 temperature class.
The DAT 420 comprises the following main parts:
The flameproof "d" metal sensing head.
The flameproof "d" metal junction box.
The flameproof "d" metal cable gland.
The 2-position terminal block for electrical connection.
The overall assembly has a flameproof "d" type of protection and an IP6X ingress protection.
Flameproof junction box
Terminal block
Mounting bracket
www.dalemans.com
Figure 2: DAT 420 detector overview
Flameproof
cable gland
Ferrite
Flameproof
sensing head
|