Connection To A Dalemans Control Unit - DALEMANS DAT 420 Instruction Manual

Gas or oxygen detecto
Hide thumbs Also See for DAT 420:
Table of Contents

Advertisement

3.4.

Connection to a DALEMANS control unit

The connection of the DAT 420 gas detector to a DALEMANS control unit requires a 2-wire cur-
rent loop. The electrical connection must be made with respect to polarity between the detector
and the control unit.
To connect the DAT 420 gas detector to a DALEMANS control unit:
Loosen the locking screw of the junction box cover using the 1.5 mm hex key and completely
turn the cover counterclockwise to unscrew it.
Loosen the cable gland cap nut, insert the cable into the cable gland and tighten.
Connect the wires to the 2-position terminal block according to the diagram below.
The cable wires must be stripped and plugged so that the gap between the wire insulation
and the metal edge of the terminal connection does not exceed 1 mm distance.
Equipotential bonding may be provided using either the internal or the external connection.
For the external connection, the bonding conductor should be at least 4 mm².
Screw the cover back onto the junction box and hand tighten ¼ turn.
Put the locking screw of the cover back in place and tighten with the 1.5 mm hex key.
The cable shielding or screening must be grounded at the control unit.
www.dalemans.com
For instructions about the electrical connection of the control unit, please refer
to the original equipment instruction manual.
Figure 7: connection to a DALEMANS control unit
Connections for
equipotential
bonding
|
14

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents