YOKOGAWA SC41 Instruction Manual page 12

2/4-electrode specific conductivity sensors
Hide thumbs Also See for SC41:
Table of Contents

Advertisement

12
FM-United States
Applying standards
Certificate no.*
Electrical data
Specific conditions
of use
Note 4
: Intrinsically safe, entity, for Class I, Division 1, Groups A, B, C and D;
Class I, Zone 0, AEx ia IIC, Ga (entity) for hazardous (classified) locations
when installed per control drawing D&E 2020-024-A50.
Maximum sensor input parameters:
Ui= 14.4 V; Ii= 116.5 mA; Pi= 0.3424 W; Li= 0 mH
Ci= 0 nF (P type) or Ci=0.4 nF (V type).
Note 5
: Ambient temperature:
-30°C to +40°C for temperature class T6,
-30°C to +95°C for temperature class T5,
-30°C to +125°C for temperature class T4 (V type),
-30°C to +130°C for temperature class T4 (P type).
-30°C to +125°C for temperature class T3 (V type),
-30°C to +165°C for temperature class T3 (P type).
When the sensor has been connected to non intrinsically safe equipment
which exceeds the restrictions regarding the sensor input circuits, the sensor
is not suitable anymore for intrinsically safe use.
* Certification is subject to change, due to new regulations or changes in the product itself.
When a certificate is updated, a new revision under the same certificate number is created
with a new date.
-
FM-United States:
FM20US0123X (effective from 03-2021)
IM 12D07J01-01EN-P
: FM Class 3600
FM Class 3610
FM Class 3810
ANSI/ISA 60079-0
ANSI/ISA 60079-11
: FM20US0123X
IS CL I, DIV 1, GP ABCD, T3...T6
CL I, ZN 0, AEx ia IIC, T3...T6 Ga
Control Drawing: D&E 2020-024-A50
: See Note 4
: See Control Drawing D&E 2020-024-A50. (Page 13-16)
Temperature classes for SC42 models are defined
T3...T6, see Note 5