Installation guide
Thermostat
Type KPU
Application
KPU thermostats are used for regulation and to ensure safety
in refrigeration, freezing, air conditioning, ventilating and
heating systems.
KPU thermostats are available with vapor charge or with
adsorption charge.
All KPU thermostats are fitted with Single-Pole Double-Throw
(SPDT) switches.
Product Specification
Charge
Type
KPU 61
KPU 61
KPU 61B
KPU 61B
KPU 61
Vapor
KPU 62
KPU 63
KPU 63
KPU 68
KPU 69
KPU 62
KPU 73
KPU 73
KPU 73B
KPU 73
Adsorption
KPU 71
KPU 71B
KPU 74
KPU 74B
KPU 75
KPU 77
man. (min.): Manual reset after cut-out on falling temperature.
1)
The switch differential is dependent on range settings. Low range settings increases the differential.
2)
High range settings decreases the differential. Use the graphs on page 3 to determine the correct differential setting.
Thermostat bulb types
A
straight capillary tube
© Danfoss A/S (AC-MC / jmn), 2014-02
Capillary tube
Code no.
Bulb type
060L5201
A
060L5203
B
060L5204
B
060L5205
B
060L5210
B
060L5206
C1
060L5213
A
060L5214
B
060L5215
C1
060L5217
B
060L5207
C2
060L5208
E3
060L5209
E1
060L5211
E3
060L5212
D
060L5218
E2
060L5216
E2
060L5219
E1
060L5220
E1
060L5221
F
060L5223
E3
B
C
remote air coil
air coil/room sensor
DKRCC.PI.CD0.A3.22 / 520H8467
For large a.c. motors and for all d.c. motors, KPU is installed
in the control circuit. For single phase ac motors, KPU
is installed in the line voltage supply to the motor.
The standard KPU enclosure is rated NEMA 1.
NEMA 1 is obtained when the thermostat is mounted on a flat
surface. When mounting KPU on a bracket, cover all unused
holes.
Regulating
Reset
length
range
function
[in.]
[°F]
80
auto.
-20 – 60
80
auto.
-20 – 60
80
man. (min.)
1)
-20 – 60
200
man. (min.)
1)
-20 – 60
80
auto.
-20 – 60
0
auto.
-20 – 60
80
auto.
-60 – 15
80
auto.
-60 – 15
0
auto.
25 – 95
80
auto.
25 – 95
0
auto.
-20 – 60
80
auto.
-15 – 60
80
auto.
-15 – 60
80
man. (min.)
-15 – 60
1)
80
auto.
-15 – 60
80
auto.
25 – 70
80
man. (min.)
25 – 70
1)
80
auto.
0 – 80
80
man. (min.)
1)
0 – 80
80
auto.
30 – 95
80
auto.
60 – 140
D
double contact remote coil
Max. bulb
Ambient
Differential Δt
temperature
temperature
[°F]
[°F]
4 – 18
250
2)
4 – 18
2)
250
5 (fixed)
2)
250
5 (fixed)
2)
250
4 – 18
2)
250
4 – 18
2)
250
10 – 25
250
2)
10 – 25
250
2)
5 – 22
250
2)
5 – 22
250
2)
-40 – 122
4 – 15
175
(170 for max.
5 – 35
175
15 – 45
175
6 (fixed)
175
5 – 35
175
5 – 18
175
5 (fixed)
175
9 – 35
175
10 (fixed)
175
5 – 18
230
6 – 18
265
E
F
remote bulb
remote duct coil
[°F]
2 hours)
1

Advertisement

loading

Summary of Contents for Danfoss KPU 61

  • Page 1 High range settings decreases the differential. Use the graphs on page 3 to determine the correct differential setting. Thermostat bulb types straight capillary tube remote air coil air coil/room sensor double contact remote coil remote bulb remote duct coil © Danfoss A/S (AC-MC / jmn), 2014-02 DKRCC.PI.CD0.A3.22 / 520H8467...
  • Page 2 16 A 16 A 10 A 112 A 12 W 400 V 220 V The terminal block as well as grounding screw are accessible after dismounting the front cover. DKRCC.PI.CD0.A3.22 / 520H8467 © Danfoss A/S (AC-MC / jmn), 2014-02...
  • Page 3 A: Manual trip. Push the lever. Use fingers only! B: Manual reset button (only on versions sold with manual reset function) C: Terminal block D: Grounding screw [°F] LSP [°C] -25 -20 © Danfoss A/S (AC-MC / jmn), 2014-02 DKRCC.PI.CD0.A3.22 / 520H8467...
  • Page 4 (at least three times) under normal E: Cover screw operating conditions. Manual switch Available only on KPU 61 (060L5210) and KPU 62 (060L5207), manual switch the manual switch is a two-position switch used to shut down the refrigeration system. The two positions are: 1.

This manual is also suitable for:

Kpu 61bKpu 62Kpu 63Kpu 68Kpu 69Kpu 73 ... Show all