Introduction

nApplications/Functions/Specifications
Applications/Functions/Specifications
• Applications
The Digital Input/Output Relay Interface is used to control air conditioners by interlocking them with
electric lock signals and fire alarm signals, and to transmit air conditioner failures to other devices.
Functions
The Digital Input/Output Relay Interface connects non-voltage contact signals, transmits their input
status to the Touch Screen Controller, and outputs signals from the contacts (open collector) according
to the command from the Touch Screen Controller.
• Specifications
Power supply
Power consumption
Operating temperature/
humidity
Storage temperature
Chassis material
Dimensions
Mass
External View
Grommet for
power input
220 - 240 V, AC 50/60 Hz
6.5 W
0 to 40 °C, 10 to 90% RH
-20 to +60 °C
Galvanized sheet metal 0.8t
(no coating)
66(H) x 193(W) x 246(D) mm
1.65 kg
234
220
246
Digital
Input type
input
Input points
Input registance
Input "ON" current
Digital
Output type
output
Output points
Output current
Output voltage
External power supply for
Input/Output
2
Photo-coupler insulation
8 points
9 k ohm
1 mA
Open collector
4 points
Max. 35 mA (per point)
Less than DC 24V
DC 12 V, 120 mA
Grommet for
Digital Inputs
Grommet for
RS485
Grommet for
Digital Outputs

Advertisement