6. ELECTRIC INSTALLATION

Electric Connection
The fan is designed for 220-240V/50Hz (single-phase) and 380-415V/50Hz (three-phase) alternating current mains.
The fan shall be connected to power supply by means of insulated, durable and thermal-resistant cords (cables, wires).
Electric wiring must be in accordance with technical connection regulations and local ordinances and national electric codes as
per enclosed wiring diagram in the terminal box or on the casing.
The recommended wire cross section is minimum 0.75 mm2.
The actual conductor cross-section selection must be based on its type, maximum permissible heating, insulation, length and
installation method (in the air, pipes or inside walls). Connect the cables to the terminal block incorporated inside the terminal
box located on the fan casing in compliance with the fan wiring diagram and the terminal designation. The terminal designations
are shown on the sticker inside the fan casing.
Check that supply is according to data on nameplate.
Insert cable according to the instructions in the junction box and seal it (Avoid water enter). The equipment connected ground
for motor protection according to the instructions - Unless the guarantee isn't accepted. Connect electric supply.
After connecting the wiring, install the terminal cover with screws.
Wiring Diagram
In the case of reverse direction of rotation:
With 1 phase motor to change direction of rotation, transpose the position of leads black and brown.
Ÿ
With 3 phases motor to change direction of rotation transpose two of the phases.
Ÿ
Black
Blue
Motor
Capacity
Brown
Yellow Green
MCB
L
AC
N
~ 220-240V
50 Hz
PE

7. INSTALLATION METHOD

Take care of direction of air flow shown by arrow
stickers.
Plate mounted wall fans with square inlet cone plate.
Installation only on a flat surface on the drilled holes in
the inlet cone plates. Installation on an uneven
surface may lead to deformation of the wall ring and
may result in the impeller rubbing the fan casing.
Make a frame or install direction in the wall.
The sizes of frame and hole refer to the above
dimension sheet.
Install the fan with screws to the frame or wall
(refer to the right picture).
www.breeze.com.vn | breezefans@breeze.com.vn
Terminals
L
Brown
FU
N
Blue
Yellow
Green
Fan
1
L
2
3
N
4
Reversible in single phase
Motor
Yellow Green
MCB
L1
AC
L2
~ 380-415V
50 Hz
L3
PE
Fig 01
Fig 03
USER'S MANUAL
AWS SERIES
Terminals
Brown
FU
Blue
Capacity
Black
Fan
U
1
Black
V
2
Blue
W
3
Brown
Yellow
Green
Fig 02
Fig 04
L
Brown
N
Blue
PE
Yellow
Green
05