EXTENDED COVERAGE, QUICK RESPONSE, LIGHT HAZARD
PENDENT AND RECESSED PENDENT SPRINKLER
GENERAL DESCRIPTION
Globe Series GL-QR/ECLH sprinklers are Listed Quick Re-
sponse sprinklers which utilize a 3mm frangible glass bulb
as the thermosensitive operating element. These sprinklers
are available in pendent and recessed pendent orientations.
They are Listed and Approved as Extended Coverage sprin-
klers for Light Hazard Occupancies for a maximum cover-
2
age area of 400 ft.
and are to be installed in accordance
with the guidelines of the appropriate Installation Standard
being mandated by the AHJ (i.e. NFPA 13). These sprin-
klers are available with a K-factor of 5.6 (80,6), a 1/2" npt
and various temperatures and finishes as shown. Recessed
escutcheon provides a total of 3/4" vertical adjustment.
OPERATION
Upon exposure to heat such as from a fire, the fluid in the
bulb expands, compressing the air bubble within the bulb.
When the air bubble can no longer compress, the fluid ex-
pansion causes breakage of the glass bulb, resulting in re-
lease of the water seat assembly, and discharge of water
from the sprinkler.
FINISHES AND ACCESSORIES
Finishes
Factory Bronze
Chrome
Black Polyester - special order
Escutcheons
Brass
Chrome
White Polyester
Stainless Steel
Wrenches
Standard
Recess
1/2" NPT
Note:
Users should refer to Globe's web site (www.globesprinkler.com)
to assure that the most recent technical literature is being utilized.
MAR 2020
4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 •
SERIES GL-QR/ECLH
K-FACTOR: 5.6
White Polyester
Black Polyester
Technical Support
989-414-2600
PENDENT
TECHNICAL DATA
SIN
GL5614
Approvals
cULus
Maximum Working Pressure
175 psi (12 bar)
Minimum Operating Pressure
See TABLES A & B
Minimum Spacing
8 ft. (2.4 m)
Temperature Rating
See TABLES A & B
Materials of Construction
Frame - bronze
Bulb seat - copper
Spring - nickel alloy
Bulb - glass with alcohol based solution, 3mm
Escutcheon Assembly - steel
GFS-200
www.globesprinkler.com
• techservice@globesprinkler.com
RECESSED PENDENT
Deflector - brass
Screw - brass
Seal - teflon
PAGE 1 of 3

Advertisement

loading

Summary of Contents for Globe GL-QR Series

  • Page 1 PENDENT AND RECESSED PENDENT SPRINKLER K-FACTOR: 5.6 GENERAL DESCRIPTION Globe Series GL-QR/ECLH sprinklers are Listed Quick Re- sponse sprinklers which utilize a 3mm frangible glass bulb as the thermosensitive operating element. These sprinklers are available in pendent and recessed pendent orientations.
  • Page 2 INSTALLATION Caution: Do not install any bulb-type sprinkler if the bulb is cracked or there is loss of liquid from the bulb. Sprinklers should be tightened enough to obtain a leak-tight joint when water pressure is applied and/or hydrostatic test is performed. Sprinklers should not be overtightened as this can result in distortion and subsequent leak- age.
  • Page 3 ORDERING INFORMATION Prior to installation, it is important to read and follow the SPECIFY: “Sprinkler Caution” sheet (GFS-840) included within each • SPRINKLER box of sprinklers. This sheet is available on Globe’s web • Quantity • • Temperature Rating •...

This manual is also suitable for:

Eclh seriesGl5614