ä ä ä ä DESIGO Installation guide Siemens Building Technologies CA2Z3884en Building Automation 08.2001...
Page 2
Siemens Building Technologies Installation guide CA2Z3884en Building Automation 08.2001...
Page 3
AC 230 V supply cables ................5 AC 24 V transformer sizing ................5 Signal cables ....................5 Cables for AC 24 V triac outputs and AC 24 V supply......6 Relay outputs....................7 Siemens Building Technologies Installation guide CA2Z3884en Landis & Staefa Division 08.2001...
Page 4
Foil screen Vapor-plated screen Unsatisfactory Do not use cables of less than the specified cable cross-section. Conductors must Cable cross-section not be wired in parallel as a means of increasing the cross-section. Siemens Building Technologies Installation guide CA2Z3884en Building Automation 08.2001...
Page 5
Max. length of single conductor where A ≥ 1.0 mm Room unit : 125 m (and see table) Cable type: 2-core, twisted pair, unscreened Diameter Max. length of single cable [mm] 1.00 1.15 0.75 0.98 0.50 0.80 Siemens Building Technologies Installation guide CA2Z3884en Building Automation 08.2001...
Page 7
The maximum resistive load is 1.8 kW. Loads above this value cause excessive wear of the contact in the case of PWM operation An external fuse of max. 10 A must be provided to protect the pcb tracks in the controller. Siemens Building Technologies Installation guide CA2Z3884en Building Automation...