Cable type
VDE / DIN
AWG
10
YSLY
12
YSLY
14
LiYYP
16
LiYYP
18
LiYYP
20
LiYYP
22
LiYYP
(G51/G87)
LiYYP
24
26
LiYYP
6/8
Siemens Building Technologies
Building Automation
5
Cables for AC 24 V triac outputs
and AC 24 V supply
The following applies to the cables of devices such as valves, damper actuators and
contactors connected to the triac outputs of the room controller:
– Use twisted, 2-core or multi-core round cable without a screen (standard installation
cable)
– Single conductors must not be used
– The conductors may be routed together with mains cables (AC 230 V), but they
MUST be insulated from the mains in accordance with regulations and in compliance
with SELV requirements.
– These conductors must NOT be run in the same cable as mains conductors
– For max. cable lengths, see the table below
A
R
Diameter
[mm 2 ]
[mm]
[Ω/km] 8.5 VA 9.5 VA
5.26
2.59
3.8
4.00
2.26
5.0
3.10
2.05
6.3
2.50
1.80
8.0
1.95
1.62
11
1.50
1.40
14
1.23
1.30
16
1.00
1.15
20
0.96
1.02
21
0.75
0.98
26
0.56
0.81
33
0.50
0.80
39
0.34
0.64
56
0.28
0.60
64
0.25
0.57
77
0.22
0.51
85
0.15
0.40
130
0.14
0.39
138
Installation guide
Cable length L max [m]
13 VA 20 VA
420
-
280
180
320
-
210
138
250
-
165
108
200
167
130
86
160
130
100
68
120
100
80
52
100
82
65
42
80
67
53
34
78
64
51
33
61
50
40
26
45
37
30
20
40
33
26
17
28
23
18
12
22
19
15
9.7
20
-
13
8.6
18
-
11.5
7.6
12
-
8.0
5.2
11
-
7.5
-
40 VA
60 VA
80 VA
100 VA
90
60
45
69
46
34
52
36
26
43
29
22
34
22
17
26
17
13
21
14
10
17
11.5
8.6
16
11.0
8.3
13
8.6
6.5
10
6.4
4.8
8.5
5.8
4.3
5.8
3.9
-
4.8
-
-
-
-
-
-
-
-
-
-
-
-
-
-
120 VA
36
30
28
23
21
18
17
14
13
11
10
8.5
8.5
7.0
6.9
5.5
6.6
5.5
5.2
4.3
3.8
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
CA2Z3884en