Lennox iHarmony 10C16 Installation And Setup Manual page 19

Damper control module
Hide thumbs Also See for iHarmony 10C16:
Table of Contents

Advertisement

MODEL
Min CFM per Schedule A
Recommended CFM on Max Kw listed @ 60° Rise
MODEL
Min CFM per Schedule A
Recommended CFM on Max Kw listed @ 60° Rise
MODEL
Min CFM per Schedule A
Recommended CFM on Max Kw listed @ 60° Rise
Notes:
All gas heat BTU based on product specification output values.
All electric heat BTU based on 3412 BTU per Kw at 240VAC. If another voltage is used
the BTU value must be taken from the EHB.
All Kw listed are single phase kits.
All S15 limits open at 150° F.
Pocket formulas (must be rounded to iHarmony increments).
CFM = BTU / 1.08 / Target Temp Rise
Temp Rise = BTU / CFM / 1.08.
Table 18. CBX32MV CFM Per Kw Range
CBX32MV-018/24
CBX32MV-024/30
2.5 - 9 Kw
4 - 15 Kw
250
250
475
800
Table 19. CBX40MV CFM Per Kw Range
CBX40MV-024
CBX40MV-030
2.5 - 9 Kw
4 - 15 Kw
250
250
475
800
Table 20. CBA38MV CFM Per Kw Range
CBA38MV-018/24
CBA38MV-030
4 - 9 Kw
4 - 15 Kw
250
250
475
800
Table 21. Schedule A
19
CBX32MV-036
CBX32MV-048
4 - 20 Kw
4 - 25 Kw
250
450
1050
1325
CBX40MV-036
CBX40MV-042
4 - 20 Kw
4 - 25 Kw
250
1050
CBA38MV-036
CBA38MV-042
5 - 20 Kw
4 - 25 Kw
250
1050
250 CFM per zone
380 CFM per zone
450 CFM per zone
CBX32MV-060
4 - 25 Kw
450
1325
CBX40MV-048
4 - 25 Kw
450
450
1325
1325
CBA38MV-048
4 - 25 Kw
450
450
1325
1325
2.5 Kw = 31.6° F rise
4 Kw = 50.5° F rise
5 Kw = 63.2° F rise
4 Kw = 33.3° F rise
4 Kw = 28.1° F rise
CBX32MV-068
5 - 25 Kw
450
1325
CBX40MV-060
4 - 25 Kw
450
1325
CBA38MV-060
4 - 25 Kw
450
1325