Outdoor Unit Pressure Value Andtotal Electric Current Curve - Fujitsu R410A Service Instruction

Split type room air conditioner
Hide thumbs Also See for R410A:
Table of Contents

Advertisement

3-2.
OUTDOOR UNIT PRESSURE VALUE AND TOTAL ELECTRIC CURRENT CURVE
Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : ASU18RLF
[Condition]
Ambient temperature : Indoor / Outdoor - Same temperature
Refrigerant amount : Standard amount
Piping length : 25ft. (Height difference 39inch. ) 7.5m (Height difference 1m)
Power voltage : 60Hz - 230V
Operation condition : TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
Measuring : method : Measure the low pressure with the pressure meter at the service valve.
Measure the outdoor unit overall current with the current clamp meter at Power Cable.
Caution : Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Cooling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
(MPa) [psi]
(1.3)
188.5
(1.2)
174.1
(1.1)
159.5
(1.0)
145.0
(0.9)
130.5
(0.8)
116.0
(0.7)
101.5
59
(15)
(20)
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
7.0
6.5
6.0
5.5
5.0
4.5
4.0
59
(15)
(20)
RH70%
RH60%
RH50%
68
77
86
(25)
(30)
In/Outdoor ambient temperature
RH70%
RH60%
RH50%
68
77
86
(25)
(30)
In/Outdoor ambient temperature
03-07
[°F]
95
(35)
(°C)
[°F]
95
(35)
(°C)