Fujitsu R410A Service Instruction page 37

Split type room air conditioner
Hide thumbs Also See for R410A:
Table of Contents

Advertisement

Trouble shooting 12
OUTDOOR UNIT Error Method:
Compressor Thermistor Error
Detective Actuators:
Outdoor Unit Main PCB
Compressor Temperature Thermistor
Forecast of Cause:
1. Connector connection failure
Test 1 : Check connection of connector
Check if connector is removed.
Check if connector is erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or miss-wiring, reset the power.
OK
Test 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
Temperature
(°C )
Temperature
(°F )
Resistance value (k )
Temperature
(°C )
Temperature
(°F )
Resistance value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Test 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
BROWN
1
1
CN64
2
2
BROWN
3 3
BLUE
1
1
CN62
2
2
BLUE
3 3
BLACK
1
1
CN65
2
2
BLACK
3 3
BROWN
1
1
CN63
2
2
BROWN
3 3
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit
: Operation lamp: 7 times Flash, Timer lamp: 2 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 72]
Detective details:
When Compressor Temperature Thermistor open or short-circuit
is detected at power ON or while running the compressor.
2. Thermistor failure
0
5
10
15
32
41
50
59
168.6
129.8
100.9
79.1
70
80
90
100
158
176
194
212
8.7
6.3
4.6
3.4
THERMISTOR
( COMPRESSOR TEMP. )
THERMISTOR
( OUTDOOR TEMP. )
THERMISTOR
( PIPE TEMP. )
THERMISTOR
( DISCHARGE TEMP. )
02-14
3. Main PCB failure
20
30
40
50
68
86
104
122
62.6
40.0
26.3
17.8
120
248
2.0
60
140
12.3