4. DRY OPERATION
In dry operation, maximum compressor frequency is defined
by set temperature, and room temperature as below.
Zone is defined by set temperature and room temperature.
Room temperature drops
Ts+0.5°C
Ts -1.5°C
Maximum compressor frequency is defined by zone.
X zone
J zone
Y zone
X zone
J zone
Y zone
AOYG09KMCBN
AOYG12KMCBN
20 rps
16 rps
0 rps
Room temperature rises
Ts+1.5°C
Ts -0.5°C
Ts = Set temperature
AOYG14KMCBN
26 rps
22 rps
18 rps
18 rps
0 rps
0 rps