Fujitsu ASYG09KMCB Service Instruction page 49

Wall-mounted type, inverter
Hide thumbs Also See for ASYG09KMCB:
Table of Contents

Advertisement

Troubleshooting 17
Outdoor unit fan motor error
OUTDOOR UNIT Error Method:
Detective actuators:
Outdoor unit main PCB
Outdoor unit fan motor
Forecast of cause:
1. Fan rotation failure
2. Motor protection by surrounding temperature rise
3. Main PCB failure
4. Outdoor unit fan motor
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
OK
Check Point 3 : Check Outdoor unit fan motor
Check Outdoor unit fan motor. (PARTS INFORMATION 5)
>>If Outdoor unit fan motor is abnormal, replace Outdoor unit fan motor.
OK
Check Point 4 : Check Output Voltage of Main PCB
Check outdoor unit circuit diagram and the voltage.
(Measure at Main PCB side connector)
RED
1
2
3
BLACK
P650
4
WHITE
5
YELLOW
6
BROWN
7
Read wire
Red - Black
207V (AC230V-10%)~ 253V (AC230+10%)
White - Black
If the voltage is not correct, replace Main PCB.
Detective details:
When outdoor fan rotation speed is less than 100rpm in 20 seconds
after fan motor starts, fan motor stops.
After fan motor restarts, if the same operation within 60sec is repeated
3 times in a row, compressor and fan motor stops.
If
and
permanently.
FAN MOTOR
FM
DC voltage
15 1.5V
02-21
repeats 5 times in a row, compressor and fan motor stops