9 Remote Air Temperature Sensor

NO
CN15
Notes:
① Distance between the monobloc unit and the remote air temperature senor should be less than
15 meters due to length of the connection cable of remote air temperature sensor;
② Height from floor is approximately 1.5 meters;
③ Remote air temperature sensor can not be located where the area may be hidden when door is
open;
④ Remote air temperature sensor can not be located where external thermal influence may be
applied;
⑤ Remote air temperature sensor should be installed where space heating is mainly applied;
⑥ After the remote air temperature sensor is installed, it should be set to "With" through the wired
controller so as to set the remote air temperature to the control point.
Front side
NO
Electric box
Back side
Remote Air Temperature Sensor
YES
1.5 Meters
Remote Air Environment
Temp sensor
CN1
2
16
NO
NO
Doors
15K
Mini Chiller