Beluk BLR-Q(U)06/12R Reference Manual

Power factor regulator

Advertisement

Quick Links

Technical Documentation
Rev. 01
Power Factor Regulator BLR-Q(U)
REFERENCE GUIDE
POWER FACTOR REGULATOR
BLR-Q(U)
Beluk GmbH
Taubenstrasse 1
D-86956 Schongau
Germany
Tel.: +49/(0)8861/2332-0
Fax: +49/(0)8861/2332-22
e-mail:
blr@beluk.de
http://www.beluk.de

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BLR-Q(U)06/12R and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Beluk BLR-Q(U)06/12R

  • Page 1 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) REFERENCE GUIDE POWER FACTOR REGULATOR BLR-Q(U) Beluk GmbH Taubenstrasse 1 D-86956 Schongau Germany Tel.: +49/(0)8861/2332-0 Fax: +49/(0)8861/2332-22 e-mail: blr@beluk.de http://www.beluk.de...
  • Page 2 Important Notice: BLR-Q(U) with option –DM includes a rechargeable battery to run the real-time clock. To replace this battery, please send the relay to Beluk. We will forward this battery to a recycling system. Important information! If the sign aside appears besides a text passage in the manual the reader is strongly...
  • Page 3: Table Of Contents

    STEPINFO ............................10 Quickstart SETUP ..........................11 MANUAL............................... 29 DATALOGGER (option –DM)......................30 DEVICE INFO ............................30 Wiring diagrams BLR-Q(U) ..................31 BLR-Q(U)06/12R ..........................31 BLR-Q(U)06/12T........................... 32 BLR-Q(U)12RT ............................. 33 BLR-Q(U) I/O ............................34 Standard Setting ......................35 Trouble shooting ......................37...
  • Page 4 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 4 of 39 Technical Data ......................38...
  • Page 5: Installation And Connection

    Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 5 of 39 1 Installation and Connection Only qualified staff is allowed to perform the installation. All legal rules have to be ob- served and technical standards have to be met. Before connecting the device check that all connecting leads are de-energized and that current transformers are bypassed.
  • Page 6: Voltage Measuring

    Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 6 of 39 1.3 Voltage measuring Terminals Um1 and Um2 are used for voltage measuring. Effective range is 50V to 530V AC and 45Hz to 65Hz. Voltage measuring is necessary for calculation of control deviation and capacitors sizes for reactive power regulation as well as for monitoring and protecting capacitors against over- and undervoltage and THD U and for showing different measuring values.
  • Page 7: Alarm Relay

    Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 7 of 39 1.5 Alarm relay BLR-Q(U) is equipped with an alarm relay to signal proper function of the system. The alarm relay has one C/O contact. The common point is terminal M. Between the terminals M and MO is the breaking contact.
  • Page 8: User Interface

    Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 8 of 39 1.8 User Interface User Interface of BLR-Q(U) is a graphical LCD and a membrane keyboard with 4 softkeys. LCD is split into 4 areas: Top area: the two lines of top area are showing information about general status of the relay. In Voltage control mode always the actual target power factor is shown.
  • Page 9: Menu Blr-Q(U)

    Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 9 of 39 2 MENU BLR-Q(U) 2.1 MEAS. VALUES This submenu shows the available measurement values in the main area of LCD. The values can be chosen by pushing the ▲ / ▼-keys. Available measuring values: BLR-Q(U) ULL (voltage phase –...
  • Page 10: Harmonics

    Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 10 of 39 2.2 HARMONICS The BLR-Q(U) is permanently calculating the harmonics of the voltage and current by using Fourier transformation. After selecting the submenu these values are displayed separated in even and odd harmonics of current and voltage in main display area. Every displayed value is related to the fundamental wave.
  • Page 11: Quickstart Setup

    Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 11 of 39 2.3.2 SWITCH CYCLES BLR-Q(U) is counting and showing the switching cycles of each step. This value allows the conclusion about the actual state of the contactors. Switch cycles can be preset separately for each step in SETUP/STEPS (2.4.22.3).
  • Page 12 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 12 of 39 2.4.3 CT FACTOR The CT FACTOR is the ratio of current transformer. (e. g. 1000/5 = ratio 200). At BLR-Q(U)3phase the CT- Factor is used for all three current channels. For current measuring a CT always have to be used! 2.4.4 VT-FACTOR VT FACTOR is the ratio of the voltage transformer.
  • Page 13 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 13 of 39 2.4.6 CONTROL ON / FREEZE / OFF Automatic control is running FREEZE: Automatic control is stopped; status of exit relays is frozen OFF: Automatic control is stopped; all exit relays are off 2.4.7 cosϕ...
  • Page 14 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 14 of 39 2.4.9.2 DISCHARGE TIME For every single capacitor step an own discharging time can be defined. The discharging time is a blocking time, becoming active after switching off a step. As long as this time is running (display of "!" in the step indi- cation) this step is not available for the regulation.
  • Page 15 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 15 of 39 2.4.17 COS PHI : U SET POINT 4 Defines target point 4 for the COS PHI : U / COS PHI : P control SET POINT 4 uses the “COS PHI IND” when the measured voltage is at the level which is adjusted. In fac- tory setting this point is used when 1.06 * NOM.
  • Page 16 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 16 of 39 The selection can also be done manually by pushing the ◄► button. The types, "U=L-N" or "U=L-L" are available. 2.4.21.5 SYNCHRONISATION FREQUENCY For a high precision of the measurement, the sampling rate has to be synchronized to the frequency of the grid.
  • Page 17 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 17 of 39 2.4.21.11 CT TYPE 1A This setting changes some internal threshold levels, to optimize the function with 1Amp CTs. 2.4.22 STEPS Settings concerning the step data base can be found in this submenu. The following settings are possible: 2.4.22.1 DISCHARGE TIME For every single capacitor step an own discharging time can be defined.
  • Page 18 A step can be programmed as a capacitor (c) or as an inductor (i). If you plan to use a mixed mode between capacitors and inductors, please contact Beluk to get more information. At BLR-Q(U)3phase capacitor size has to be programmed for each phase individually.
  • Page 19 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 19 of 40 Between the adjusted "SET POINTS" the controll target is calculated dynamically as shown in the below drawing. This means finally that the "TARGET POINTS" are just fixing the charachteristic, the remaining tasks are done automatically...
  • Page 20 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 20 of 39 Regulation mode normal algorithm: 4 different regulation modes are available at BLR-Q(U) for standard cos phi control, in voltage control this settings does not work: 1. Auto: The controller is working with the principle of „Best Fit“. Before a switching operation, all ca- pacitor-sizes in step database are compared with control deviation.
  • Page 21 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 21 of 39 Settings concerning control functions can be found in this submenu. These settings are available: 2.4.23.1 CONTROL ON / FREEZE / OFF Automatic control is running FREEZE: Automatic control is stopped; status of exit relays is frozen OFF: Automatic control is stopped;...
  • Page 22 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 22 of 39 2.4.23.5 STEP RECOGNITION Pushing ◄►-key is changing between "ON" and "OFF". "Step recognition OFF": Capacitor sizes should be programmed manually: b) When fast-oscillating load influences automatic stepsize recognition. c) When recognition of defective steps is not wished d) When capacitor contactors are switching with a delay of more than 200msec.
  • Page 23 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 23 of 39 2.4.23.10 CONTROL Four control modes can be selected: “Best Fit“ AUTO: “Last in, first out“. LIFO: 1. Threshold level of each step is checked separately. If steps have different sizes, this can cause inaccuracy.
  • Page 24 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 24 of 39 The following items appears only when the cos phi control is set to COS Phi : U, otherwise the points are not visible. 2.4.23.15 COS PHI CAP Defines the capacitive limit for the voltage control. 2.4.23.16 COS PHI : U SET POINT 1 Defines target point 1 for the COS PHI : U / COS PHI : P control SET POINT 1 uses the “COS PHI CAP”...
  • Page 25 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 25 of 39 2.4.24 DISPLAY In this submenu settings can be made according the display. The following settings are possible: 2.4.24.1 Display The following masks can be selected for the top display area by pushing the ◄►-key. This masking is per- manently displayed.
  • Page 26 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 26 of 39 2.4.25 ALARM In the following chapter all adjustable Alarms including trigger are listed. Trigger after 50x switching time not reaching the target cosϕ and ∆Q > smallest step Control alarm (over-/under compensation) Trigger: I <...
  • Page 27 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 27 of 39 2.4.25.1 Alarmevents M relay: volt free alarm output with C/O contacts. The relay is normally active and gives signal when it drops. Max fuse 6A, breaking capacity 250V AC / 5A DO relay: digital output with N/O contact.
  • Page 28 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 28 of 39 2.4.26 MODBUS This submenu is only enabled when the regulator is equipped with the Modbus interface. The following set- tings are possible: BAUD RATE: The baud rate can be selected by pushing the ◄►-key. The valid range is between •...
  • Page 29: Manual

    Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 29 of 39 2.4.28 RESET 2.4.28.1 RESET SETUP Reset of BLR-Q(U) to factory settings without step database. 2.4.28.2 RESET FAULTY STEPS Reset of steps, which are detected as faulty, back to automatic mode. 2.4.28.3 RESET STEPS Reset of step database.
  • Page 30: Datalogger (Option -Dm)

    Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 30 of 39 2.6 DATALOGGER (option –DM) 2.6.1 SETUP-HISTORY Setup history gives infromation about the last 64 settings. It is working as ring-buffer, so the oldest informa- tion is overwritten. Setup history gives information about date and time and type of paramter which is changed. By pushing the ◄►-key, you can change to the values.
  • Page 31: Wiring Diagrams Blr-Q(U)

    Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 31 of 39 3 Wiring diagrams BLR-Q(U) 3.1 BLR-Q(U)06/12R Einspeisung Last S upply Load B LR-CM Einspeisung Last S upply Load B LR -CM...
  • Page 32: Blr-Q(U)06/12T

    Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 32 of 39 3.2 BLR-Q(U)06/12T Einspeisung Last S upply Load T riggereingang/ T riggerinput B LR-CM BEL -T SXX Einspeisung Last S upply Load T riggereingang/ T riggerinput B LR -CM BEL -T SXX...
  • Page 33: Blr-Q(U)12Rt

    Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 33 of 39 3.3 BLR-Q(U)12RT Einspeisung Last S upply Load T riggereingang/ T riggerinput B LR-CM BEL -T SXX Einspeisung Last S upply Load T riggereingang/ T riggerinput B LR -CM BEL -T SXX...
  • Page 34: Blr-Q(U) I/O

    Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 34 of 39 3.4 BLR-Q(U) I/O...
  • Page 35: Standard Setting

    Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 35 of 39 4 Standard Setting Function Factory setting Range of setting Customer setting Language English English, German, French CT-factor 1,0 – 6500,0 VT-factor 1,0 – 350,0 Nominal voltage (ph-ph) 400V 100 –...
  • Page 36 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 36 of 39 Function Factory setting Range of setting Customer setting P-export alarm disabled disabled, M, DO, D, CP, O, F Temp1 alarm disabled, M, DO, D, CP, O, F Limit temperature 1 25°C 20°C –...
  • Page 37: Trouble Shooting

    Beluk work proper...
  • Page 38 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 38 of 39 6 Technical Data Auxiliary voltage 100 - 132V / 207 - 253V, 45-65Hz, max. fuse 6A Voltage measuring 50 – 530V, 45 – 65Hz, PT-ratio 1 - 350 Current measuring 0 –...
  • Page 39 Technical Documentation Rev. 01 Power Factor Regulator BLR-Q(U) Page 39 of 39 Beluk GmbH, Taubenstrasse 1, 86956 Schongau, Germany Phone: +49 8861 23320, Fax: +49 8861 23322, blr@beluk.de http://www.beluk.de...

This manual is also suitable for:

Blr-q(u)06/12tBlr-q(u)12rtBlr-q(u) i/o

Table of Contents