17
|
Piping installation
To close the stop valve
To handle the stop valve cover
To handle the service port
Tightening torques
Installer and user reference guide
80
1 Remove the stop valve cover.
2 Insert a hexagon wrench into the stop valve and turn the stop valve clockwise.
3 When the stop valve cannot be turned any further, stop turning.
4 Install the stop valve cover.
Result: The valve is now closed.
The stop valve cover is sealed where indicated by the arrow. Do NOT damage it.
After handling the stop valve, tighten the stop valve cover securely, and check for
refrigerant leaks. For the tightening torque, refer to the table below.
Always use a charge hose equipped with a valve depressor pin, since the service
port is a Schrader type valve.
After handling the service port, make sure to tighten the service port cover
securely. For the tightening torque, refer to the table below.
Check for refrigerant leaks after tightening the service port cover.
Stop valve size
(mm)
Valve body
Ø9.5
5.4~6.6
Ø12.7
8.1~9.9
Ø19.1
27.0~33.0
Tightening torque N•m (turn clockwise to close)
Shaft
Hexagonal
wrench
4 mm
8 mm
Cap (valve lid)
Service port
13.5~16.5
11.5~13.9
18.0~22.0
22.5~27.5