PROBLEM
POSSIBLE CAUSES
The unit is not
Power failure
working
The power is turned off
The fuse is burned out
Remote control batteries are dead
The unit's 3-minute protection has
been activated
Timer is activated
ERROR CODES
CODE ERROR
E0
Indoor EEPROM malfunction
E1
Communication malfunction between indoor and outdoor unit
E2
Zero-crossing signal detection error
E3
Indoor fan speed malfunction
E4
Ambient temperature sensor (T1) malfunction
E5
Evaporator temperature sensor (T2) malfunction
EC
Refrigerant leakage detection
F0
Current overload protection
F1
Outdoor temperature sensor (T4) malfunction
F2
Outdoor condenser pipe temperature sensor (T3) malfunction
F3
Discharge air temperature sensor (TP) malfunction
F4
Outdoor EEPROM malfunction
F5
Outdoor fan speed malfunction
F6
T2B sensor malfunction (Multi-zone outdoor units only)
P0
IPM malfunction or IGBT current protection
P1
Voltage protection - DC voltage between P&N out of range
P2
High temperature protection of IPM module or compressor
P3
Outdoor temperature too low
P4
Inverter compressor drive error
P6
High/Low pressure protection
NOTE
If your problem persists after performing the checks and diagnostics above, or the error
code remains, turn off your unit immediately and contact an authorized service center.
22
SOLUTION
Wait for the power to be restored
Turn on the power
Replace the fuse
Replace batteries
Wait three minutes after restarting the
unit
Turn timer off
DURASTAR.COM
Need help?
Do you have a question about the DRAW09F1A and is the answer not in the manual?