Vibration Level - Mitsubishi Electric CITY MULTI PURY-HP72TNU-A Data Book

Air conditioning systems
Table of Contents

Advertisement

6. VIBRATION LEVEL

6. VIBRATION LEVEL
[PURY-HP72-120T/YNU, PURY-HP144-240T/YSNU]
Measurement condition
Measurement frequency: 1 Hz-80 Hz
Measurement point: Ground surface 20 cm away from the unit leg
Installation condition: Direct installation on the concrete floor
Power source: 3-phase 3-wire 208 V-230 V 60 Hz: For TNU-Series
3-phase 3-wire 460 V 60 Hz: For YNU-Series
Operation condition: JIS condition (cooling, heating)
Measurement device: Vibration level meter for vibration pollution VM-1220C (JIS-compliant product)
Concrete
10cm
Vibration level
Model
PURY-HP72T(Y)NU-A
PURY-HP96T(Y)NU-A
PURY-HP120T(Y)NU-A
PURY-HP144T(Y)SNU-A
PURY-HP192T(Y)SNU-A
PURY-HP240T(Y)SNU-A
* Vibration level varies depending on the conditions of actual installation site.
MEES19K180
Service panel side
Measurement point
Vibration level (dB)
46
46
47
49
49
50
20cm
Hyper Heating Inverter R2-Series
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents