6.11 Dip Switch Settings

DIP Switches
1 -> 3
1
off
on
off
on
off
off
on
4 -> 5
4
off
on
off
on
6 -> 7
6
off
off
8
8
off
on
9 -> 10
9
off
on
off
on
11
11
off
on
12
12
off
on
13
13
14
14
15
15
16
16
© Obelux Oy 2016
2
3
Flashing sequence selection.
off
off
Steady burning. All active channels.
off
off
60 flashes / minute
on
off
40 flashes / minute
on
off
20 flashes / minute
off
on
BMVBW sequence: 1s on - 0.5s off - 1s on - 1.5s off.
on
on
30 flashes / minute
on
on
RESERVED
5
Flash duration.
off
100 millisecond flashes.
off
250 millisecond flashes.
on
500 millisecond flashes.
on
CASA Flash duration (Duty cycle: 2/3 ON, 1/3 OFF)
7
Flashing mode.
off
All active Outputs flash together.
on
Outputs 1-3 are flashing together, output 4 is steady burning.
Test mode enable
Normal operation
Test mode. (*See documentation for information about test mode)
10
Photocell operation (External and Internal photocell)
off
Photocell not used.
off
Lights are disabled if lighting level is above 400 lux.
on
Lights are disabled if lighting level is above 800 lux.
on
Lights are disabled if lighting level is above 1600 lux.
External / Internal photocell selection.
Use internal photocell
Use external photocell
Main / Spare operation select.
Normal operation
Main / Spare operation.
Option1
Option2
Option3
Option4
Obelux Oy, Kutomotie 6 B, 00380 Helsinki FINLAND
Technical information in this document is subject to change without notice.
CSW-DCW – Manual