Photocell Operation; Main/Spare Operation; Options; Alarm Windows - OBELUX CSW-DCW Manual

Fault monitoring, switch-over and flash controller unit
Table of Contents

Advertisement

6.6 Photocell operation

DIP switch named EXT/INT PHOTOCELL selects internal photocell.
(off) Internal photocell is used.
(on) External photocell is used.

6.7 Main/Spare operation

DIP switch named MAIN/SPARE set the main/spare operation.
First pair:
Output 1 (Main 1)
Output 2 (Spare 1)
Second pair
Output 3 (Main 2)
Output 4 (Spare 2)

6.8 Options

DIP switches named OPTION 1, 2, 3, 4 must be set to off in normal operation. If DIP switches Option 1 or 2
are turned on, the CSW will function in modus mode. In this mode it will listen to commands from the RS485
bus. This functionality is not covered in this manual.

6.9 Alarm windows

All four channels have their own rotary switch dials to select minimum and maximum alarm limits. Alarm
window is selected by turning the dials with a flathead screwdriver to the wanted setting. Each number
represents a certain power limit. For example, selecting number 4 from the MIN dial and number 5 from MAX
dial selects the alarm window to be from 5W to 20W. If the power consumption on that channel is outside
this window the alarm is triggered. If the lights are used in flashing mode, the maximum alarm limit must be
selected according to the maximum power consumption during the flash pulse.
When both MIN and MAX dials are set to zero position, the output channel is disabled.
#
MIN
0
OFF
1
0.3W
2
1W
3
2W
4
5W
5
10W
6
15W
7
20W
8
35W
9
50W
Table 2: Alarm window settings
© Obelux Oy 2016
MAX
OFF
3W
5W
10W
15W
20W
35W
50W
80W
120W
Obelux Oy, Kutomotie 6 B, 00380 Helsinki FINLAND
Technical information in this document is subject to change without notice.
CSW-DCW – Manual
Page: 12(17)