6 CONFIGURATION

This chapter describes the configuration of the CSW-DCW board. The configuration is carried out by setting
the 16 DIP switches on the CSW-DCW board. OFF position for a dip-switch is towards the left edge of the
CSW-DCW board.
Having all 16 DIP switches to OFF is a special case. CSW-DCW reads stored configuration from memory
and starts using this configuration if it is a valid one. If there is no valid configuration, the CSW-DCW uses
configuration where all DIP switches are set to OFF. This configuration disables all channels.
Figure 2: DIP switches in off position

6.1 Base sequence

DIP switches named FLASH SEQ 1, 2, 3 select the Base Sequence.
(off,off,off) Selects always Steady-burn.
(on,off,off) Selects 60 flashes per minute total. (One flash / second)
(off,on,off) Selects 40 flashes per minute total. (One flash / 1.5 seconds)
(on,on,off) Selects 20 flashes per minute total. (One flash / 3 seconds)
(off,off,on) Selects the BMVBW flash sequence. 1s on - 0.5s off - 1s on - 1.5s off
Please note: Set DIP switches 4 and 5 to OFF when using this base sequence.
(off,on,on) Selects 30 flashes per minute total. (One flash / 2 seconds)
Any other selection is RESERVED for future expansions.