Samsung MIM-E03CN Installation Manual page 11

Air to water heat pump control kit
Hide thumbs Also See for MIM-E03CN:
Table of Contents

Advertisement

No.
Thermistor
CNS043(White)
1-2: Heater Out
5-6: Eva In
TB-C(Black)
F1-F2:COMM1 (IN-OUT COMM)
Flow Sensor
CNS057(White)
1: DC5V
2: Signal
3: Gnd
4: N.C
Immersion Heater
TB-A1(Block)
L-N, Output, AC
TB-B(Black)
Terminal No.
Function
B1/B6
Water Pump
B2/B3/B5
Mixing valve
B4/B5
Backup Boiler
B7/B8
Water Pump
B9/B10/
2Way valve #1
B11/B12
B13/B14/B11/
2Way valve #2
B12
B15/B16/B17/
3Way valve
B18
B19/B20
Thermostats
B21/B22
Thermostat 1
B23/B24
Thermostat 2
B25/B26
Solar Pump
Dip Switch(K1~K4)
Note
Input /output
Max. Current
AC 230V output
AC 230V output
22 mA
AC 230V output
10 mA
AC 230V output
AC 230V output
22 mA
AC 230V output
22 mA
AC 230V output
22 mA
AC 230V output
22 mA
AC 230V input
22mA
AC 230V input
22mA
AC 230V input
10 mA
No.
TB-C(Black)
F3-F4:COMM2 (Wired Remote Controller)
Water Pump Signal
CNS1(White)
1: Signal
3: Gnd
3-Way Valve
CNP501(White)
1: Neutral
3: Signal_NO
5: Signal_NC
Main Power TB-A(Black)
L-N, INPUT, AC
Description
Water INV. pump operation (maximum input power of
0.5 A
pump 100W). (B6 : Lived)
Mixing Valve operation(B2: CW, B3: CCW)
Signal output for Backup Boiler(B5: Neutral)
Additional Water pump operation (maximum input
0.5 A
power of pump 100W)(B8 : Lived)
2 Way Valve operation for Zone#1 (UFH)
(B9 : NO, B10 : NC, B11: Neutral, B12: Lived)
2 Way Valve operation for Zone#2 (FCU)
(B13 : NO, B14 : NC, B11: Neutral, B12: Lived)
3 Way Valve operation for DHW
(B17 : NO, B18 : NC, B15: Neutral, B16: Lived)
Power to external thermostat(s)
(B20: Lived)
Thermostat for zone#1 (UFH) Cooling(B21)/
Heating(B22) Signal
Thermostat for zone#2 (FCU) Cooling(B23)/Heating(B24)
Signal
Signal input from Solar Pump / DHW Thermostat
(B26 :Lived)
Note
Remark
Mandatory
Option
Option
Option
Option
Option
Option
Option
Option
Option
Option
11

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents