Cabinet and Rack Installation
This appendix includes the following information:
•
•
Cabinet and Rack Requirements
This section provides the Cisco MDS 9000 Family requirements for the following types of cabinets and
racks, assuming an external ambient air temperature range of 0 to 40°C:
•
•
•
•
Note
If you are selecting an enclosed cabinet, we recommend one of the thermally validated types listed
above: standard perforated or solid-walled with a fan tray.
General Requirements for Cabinets and Racks
The cabinet or rack must be one of the following rack types:
•
•
The cabinet or rack must also meet the following requirements:
•
•
OL-20185-01
Cabinet and Rack Requirements, page 1-43
Cisco MDS 9000 Family Telco and EIA Shelf Bracket, page 1-45
Standard perforated cabinets
Solid-walled cabinets with a roof fan tray (bottom to top cooling)
Standard open racks
Telco racks
Standard 19-in. four-post EIA cabinet or rack, with mounting rails that conform to English universal
hole spacing per section 1 of ANSI/EIA-310-D-1992. See the
Cabinets" section on page 1-44
page
1-45.
Standard two-post telco rack, with mounting rails that conform to English universal hole spacing per
section 1 of ANSI/EIA-310-D-1992. See the
page
1-45.
The minimum vertical rack space per chassis should be 1 RU (rack unit), equal to 1.75 in. (4.4 cm).
The width between the rack-mounting rails must be at least 17.75 in. (45.1 cm). For four-post EIA
racks, this is the distance between the two front rails.
C H A P T E R
and
"Requirements Specific to Solid-Walled Cabinets" section on
"Requirements Specific to Telco Racks" section on
Cisco MDS 9148S Multilayer Switch Hardware Installation Guide
1
"Requirements Specific to Perforated
1-43