Follow these installation instructions during installation. Please do not make any
changes to components. Install the device completely before putting the device
into operation.
To avoid the risk of electric shock, note the following:
a) Use this device only as intended by the manufacturer. If you have any
questions, please contact the manufacturer or your local service partner.
b) Always disconnect the unit from the power before maintenance or cleaning
work.
The mounting of the suspension elements must be carried out by a qualified
specialist. The fan´s wings have to be installed at least 3.5 m above the floor.
Do not operate or install a big fan or individual parts that are damaged. If the fan
does not work properly or if there are any unusual movements of the fan, switch
off the power supply and contact your customer service.
Make sure that the replacement of in particular safety-related parts, is carried out
by the manufacturer, its customer service or a qualified specialist.
Install the safety cables on each fan according to the installation instructions. The
MonsterFans must never be operated without a properly installed safety cable. In
an emergency, the safety ropes additionally secure the fan. Proper installation of
the ropes is also required for the stabilisation during operation. The fan shall not be
operated in windy surroundings.
We recommend also securing the floor under the assembly so that attention is
drawn to the work on the ceiling. Review all relevant guidelines to ensure that
building regulations are followed in accordance with product certifications.
We always recommend having a structural engineer check who confirms the
strength of the building and ceiling structure in advance.
If MonsterFans are located in closed rooms with heaters with indirect exhaust gas
systems (unflued), the parallel operation must be prevented by interlocking it!
2.1 Placement & Distances
Before installing the fans, check compliance with all guidelines for fire alarm systems, sprinkler
systems and fans. We strongly recommend consultation with your local safety expert.
If sprinkler systems are installed, the fans must not interfere with the proper operation of these
sprinklers. The control unit can also be connected to a fire alarm system so that the fan stops
in an emergency.
The digital inputs and the Modbus interface of the control units are used for switching off and
interlocking. If possible, do not mount the fan directly under lights to avoid adverse lighting
effects from rotating wings.
If the building has a mezzanine, fans should be installed in the way that they are not
accessible to people. HVLS fans should not be installed in the immediate vicinity of air supply
outlets or suction inlets of other heating, ventilation or air conditioning units, see chapter 4.2.