Disclaimer WILO Mather and Platt is very grateful for your interest in its products. The basic objective of this document is to provide instructions for maintaining and operating WILO Mather and Platt Sump Pumps. Instructions are compiled for the person having a working knowledge of Sump Pumps and the pumps shall be installed under expert supervision and guidance.
Page 3
Fig. 1: Lifting of complete pump: (See Page No. 15; Point no. 3.1) CAUTION! : Do not lift the Pump with motor. Always dismantle the motor before lifting the pump unit. Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 4
Fig. 2: PNV pump with self-lubrication: (See Page No. 23; Point no. 9.3.1.2) Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 5
Fig. 3: PNV pump with external water lubrication: (See Page No. 23; Point no. 9.3.1.1) Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 6
Fig. 4: PNV pump with grease lubrication: (See Page No. 23; Point no. 9.3.1.3) Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 7
Fig. 5: Auxiliary Oil Pumps (AOP): (See Page No. 23; Point no. 9.3.2) Fig. 6: Emergency Oil Pump (EOP): (See Page No. 23; Point no. 9.3.2) Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 8
Fig. 7: 4/5 SR.12 KL Model 70 Pump (See Page No. 24; Point No. Technical Data) Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 9
Fig. 8: 5/6 EHLG Pump (See Page No. 24; Point No. Technical Data) Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 10
Fig. 9: 8/8 Series 6 Model 60 (See Page No. 24; Point No. Technical Data) Fig. 10: Suction Pipe details: (See Page No. 21; Point No. 7.6.2) Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 11
Fig. 11: Mechanical seal arrangement (On request): (See Page No. 17; Point No. 4.5) Fig. 12: Thrust bearing arrangement: (See Page No. 23; Point No. 9.3.2) Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 12
Fig. 13: Alignment of pump-motor coupling: (See Page No. 25; Point No. 9.7) Fig. 14: Details of Flexible coupling: (See Page No. 25; Point No. 9.7) Fig. 15: Details of Muff coupling assembly: (See Page No. 28; Point No. 10.5) Installation and operating instructions WILO Mather and Platt – Sump Pumps...
• Loss of any claims to damages be filled out completely. By signing this list, all persons working • WILO Mather and Platt does not accept any liability for on or with the product confirms that they have received, read damage, failures or losses arising due to improper and understood this operating &...
To lift the pump see lifting diagrams - see also general safety Information, point 2 Page No. 14) these must have sufficient load bearing capacity to ensure that the product can be transported safely. Installation and operating instructions WILO Mather and Platt – Sump Pumps...
It is suggested that the check of parts & material against the bill 3.5 Intended use of materials be made jointly with the WILO Mather and Platt representative & customer representative. The pump supplied is intended for specific fluid. Refer pump data sheet and order confirmation.
It is included in standard scope of supply. It brings the pump liquid to mounting plate level. Delivery pipe flanges are as per ANSI 150 class FF or RF. We can also supply as per IS6392 table no. 17 Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Recommended Notes: 25 % Power Margin • For Forged Steel / Cast Steel MOC kindly contact WILO Mather and Platt. • Specified gap to be maintained between pump and motor half Example: • Duty point: 100 m3/h – 30 m – pump efficiency 78 % coupling.
The wedges must be able to support the weight of the entire pumping assembly and hold the assembly steady enough that no excess vibration occurs. Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 21
This flow can reverse rotation of Check to see that connections are made to the lubrication the pump, potentially damaging the pump, motor and fittings at pump manifold on mounting plate. associated equipment. Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Bearings are given an initial charge of grease before leaving WILO Mather & Platt works and do not require any attention beyond the normal greasing routine before the first Capacity Connection...
Page 24
Installation and operating instructions WILO Mather and Platt – Sump Pumps...
In the event of any malfunction of the equipment, switch off the pump set. When the pump has come to rest, close the discharge valves, isolate the driving unit power supply & rectify the fault. Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Refer Motor / Engine manufacturers manual for the • Vibration & sound level readings should be taken once in a respective routine maintenance checks. fortnight and values compared with that of previous records. Installation and operating instructions WILO Mather and Platt – Sump Pumps...
• Remove the intermediate bracket/support pipe assembly • A crane / chain pulley block suitable for handling the weight fasteners and remove top support pipe. of pumping unit. Installation and operating instructions WILO Mather and Platt – Sump Pumps...
• Check that bearing rotates freely and smoothly. If there is any doubt i) Repeat the same procedure till top shaft. (Ref. fig. 15; regarding the serviceability of the bearing it should be renewed. Page No. 12) Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Grease the bearing with the help of grease gun. For further greasing the bearing a separate grease feeder is supplied along with the pump, which is mounted side of the motor stool. Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Check the causes and refer to M&P. Measure with pressure head gauge Specific gravity of liquid different from design Refer to WILO Mather and Platt Viscosity of liquid different from design Refer to WILO Mather and Platt Installation and operating instructions Wilo Mather and Platt –Sump Pumps...
Operation at very low capacity Check the causes and refer to M&P, operate pump at rated Duty Parallel operation of pumps unsuitable for such Refer to WILO Mather and Platt with characteristics curves of pump Operation Foreign matter in impeller Open and clean...
Page 32
Availability of sufficient cooling liquid for bearings as specified Free rotation of pump and drive shafts Lubrication of bearings Checking of insulation resistance of motor (if supplied by WILO M&P) Proper cable termination (Clients Scope) Motor Protection Relay Setting (Check with Clients)
Page 33
Discharge Pressure Voltage DE Bearing Temperature DE Bearing Temperature NDE Bearing Temperature NDE Bearing Temperature Duration of Trial Run Winding Temperature (Max.) Observations and Remarks: Customer Representative WILO M&P Representative Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 34
Pump set Levelling Record Required accuracy of pump set levelling is 0.05 mm Result: Customer Representative WILO M&P Representative Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 35
A: Before Connecting Suction and Delivery Piping: Gap Between Coupling Halves: Actual Gap: B: After Connecting Suction and Delivery Piping: Gap Between Coupling Halves: Actual Gap: Customer Representative WILO M&P Representative Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 36
Noise level measurement at Pump House Floor Noise Level in dBA: Background Noise (dBA): Instrument Details: Distance -1 mtr. from the Pump: Make: Model: Sr. No.: Customer Representative WILO M&P Representative Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 37
Vibration Measurement: (Pk to Pk) Position Displacement Velocity Displacement Velocity Displacement Velocity (mm/sec.) (mm/sec.) (mm/sec.) Pump DE Pump Motor DE Motor Instrument Details: Make: Model: Sr. No: Customer Representative WILO M&P Representative Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 38
Project: Bearing Temperature: Sr. No. Position Temperature Ambient Remarks Temperature Pump DE Pump NDE Motor DE Motor NDE Instrument Details: Make: Model: Sr. No: Customer Representative WILO M&P Representative Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 39
NOTES Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 40
NOTES Installation and operating instructions WILO Mather and Platt – Sump Pumps...
Page 41
NOTES Installation and operating instructions WILO Mather and Platt – Sump Pumps...