F5
T6A temperature sensor error
zF6
Electronic expansion valve connection error
F9
T5 temperature sensor error
FA
T8 temperature sensor error
Fb
T9 temperature sensor error
Fc
TL temperature sensor error
Fd
T7 temperature sensor error
H0
Communication error between main board and compressor drive board
H2
Qty. of outdoor unit decreases error
H3
Qty. of outdoor unit increases error
H4
Compressor inverter module protection
H5
Low pressure protection lock out (P2 3X in 60 minutes)
H6
Compressor discharge temperature protection ( P4 3X in 100 minutes)
H7
Qty. of indoor units mismatching
H8
High pressure sensor error
xH9
DC fan module protection ( P9 10X in 120 minutes)
Hb
Low pressure sensor error
yHd
Slave unit malfunction(y=1,2 ,1Hd stands for slave unit 1 error)
C7
Compressor inverter module temperature protection ( PL 3X in 100 minutes)
P1
High pressure protection
P2
Low pressure protection
P31
Primary current protection
P32
Secondary current protection
P4
Discharge temperature protection or discharge temperature switch protection
In the event of S10=ON, a forced test operation is set. However, a test operation is
U0
not performed for 30 minutes after power-on
xP9
DC fan module protection
PL
Compressor inverter module temperature protection
PP
Compressor discharge insufficient superheat protection
A0
Emergency stop
A1w
Refrigerant leakage protection
CA2
The system is connected to VRF DX AHU control box only
CA3
The system is connected only to the HT hydro module
CA4
The system is only connected to VRF DX AHU control box + HT hydro module
The system is simultaneously connected to VRF indoor + VRF DX AHU control box +
CA5
HT hydro module
Cb1
VRF indoor is beyond the connection range
Cb2
VRF DX AHU control box is beyond the connection range
Cb3
The HT hydro module is beyond the connection range
Cb4
The Qty. of IDUs connected to the system is beyond the connection range
L0
Inverter compressor module error
L1
DC bus low voltage protection
L2
DC bus high voltage protection
L3
Reserved
L4
MCE error
L5
Zero speed protection
L6
Motor parameter error
L7
Phase sequence error
L8
Compressor frequency hopping error
LA
PED software verification failed
Note:
'x' is a placeholder for the fan address, with 1 representing fan A and 2 representing fan B.
'y' is a placeholder for the address (1 or 2) of the slave unit with the error.
'z' is a number for the electronic expansion valve, with1 representing electronic expansion valve A and 3 representing
electronic expansion valve C.
'w' is a placeholder for the protection mode of refrigerant leakage, with 1 representing the system should force to shutdown
after the protection, 2 representing the system should force to shutdown after the protection in 12 hours and 3 representing
the system should force to shutdown after the protection in 24 hours.
Error or protection definition
06
Remarks
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Only displayed on the the master unit
Only displayed on the the master unit
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Only displayed on the the master unit
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Only displayed on the the master unit
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error