Function Check - Wolf MGK-130 Maintenance Instructions Manual

Gas condensing boilers
Table of Contents

Advertisement

Function check

Flue gas test
24
Function check
a) Open gas tap and check for tightness up to the GCV with a leak detector.
b) Start the boiler. The burner starts.
c) Check the joint downstream of the GCV with a leak detector.
d) Function check: Close the gas tap. Fault code 12 or indicator ring flashes red.
e) Open gas tap, press reset button. The burner shuts down.
f) Adjust parameters if changes from the factory settings are required.
g) Check the function of control accessories.
Carry out the test in emissions test mode and enter the values in the
maintenance report.
Re-adjust the CO
content if required (see also installation instructions).
2
3062882_0910