Optional Single Point Power Supply Connections - York YCUL0045 Installation Operation & Maintenance

Air-cooled condensing units r22 & hfc - 407c style c (50 hz.)
Table of Contents

Advertisement

Installation
OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTIONS – YCUL0045 - YCUL0121
One Field Provided Power Supply to the condensing unit. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused Disconnect
Switch (optional) or Circuit Breaker (optional).
TABLE 9 – OPTIONAL SINGLE-POINT POWER SUPPLY
SYSTEM #1 FIELD SUPPLIED WIRING
MIN
MODEL
N/F
VOLT
HZ MCA
1
YCUL
DISC
SW
2
380/415 50
35
60
0045
380/415 50
46
60
0061
380/415 50
53
60
0081
380/415 50
62
100
0095
380/415 50
73
100
0121
See Notes and Legend on page 38.
34
INCOMING (LUGS) WIRE RANGE
D.E. FUSE CKT. BKR.
5
FACTORY SUPPLIED OPTIONAL
MIN
MAX
MIN MAX
3
4
SINGLE POINT DISCONNECT BREAKER
40
45
40
45
# 10 - # 1
50
60
50
60
# 10 - # 1
60
70
60
70
# 10 - # 1
70
70
70
70
# 10 - # 1
80
90
80
90
# 10 - # 1
SYSTEM #1 COMPRESSOR & FAN
6
COMPR. #1 COMPR. #2
RLA LRA
# 14 - 2
# 14 - 2
12.0
99
# 14 - 2
# 14 - 2
16.6
127
# 14 - 2
# 14 - 2
19.9
167
# 14 - 1/0
# 14 - 1/0
23.9
198
# 14 - 1/0
# 14 - 1/0
19.9
167
FORM 150.63-NM6 (1020)
COMPR. #3
FANS
FLA
RLA LRA
RLA
LRA
QTY
(EA)
12.0
99
2
4.0
16.6
127
2
4.0
19.9
167
2
4.0
23.9
198
2
4.0
19.9
167
19.9
167
2
4.0
JOHNSON CONTROLS