York YCUL0045 Installation Operation & Maintenance page 60

Air-cooled condensing units r22 & hfc - 407c style c (50 hz.)
Table of Contents

Advertisement

Installation
DIMENSIONS - YCUL0125 - YCUL0185 (SI)
MODEL YCUL
A
0125
7/8" OD
0145
7/8" OD
0161
7/8" OD
0171
7/8" OD
0185
1 1/8" OD
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit
is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 2m; rear to wall – 2m; control panel to end wall
– 1.2m; top – no obstructions allowed; distance between adjacent units – 3m. No more than one adjacent wall may be higher than the
unit.
60
B
3
6
6
6
6
FORM 150.63-NM6 (1020)
LD04453A
JOHNSON CONTROLS