Toshiba Carrier MMDMMD-AP0120VHG2UL Installation, Operation And Maintenance Manual page 37

Vertical air handling unit
Table of Contents

Advertisement

SPECIAL INSTRUCTIONS—CONTROLS
■Function code (DN code) setting
DN
Items
Code
Filter display de-
01
lay timer
02
Dirty state of filter
Central control
03
address
Specific indoor
04
unit priority
05
Constant fan
Heating temp.
06
shift
Existence of
0d
[AUTO] mode
FS unit connec-
0E
tion set of multi-
ple indoor units
0F
Cooling only
10
Model code
Line (System)
12
address
13
Indoor address
14
Group address
Automatic restart
28
of power failure
HA terminal
2E
(CN61) select
Ventilation fan
31
control
Remote control
32
sensor
Temperature unit
33
select
Timer setting
60
(wired remote
controller)
77
Dual set point
Priority operation
mode
FD
(Flow selector
unit)
Alarm clearance
92
condition
Setting of
"prevention of
9B
cold air dis-
charge" control
035-000051-001
Description
0000 : None
0001 : 150H
0002 : 2500H 0003 : 5000H
0004 : 10000H
0000 : Standard
0001 : High degree of dirt
0001 : No.1 unit to 0064 : No.64 unit,
0099 : Unfixed
0000 : No priority
0001 : Priority
0001 : L tap during heating thermo-off
0012 : Fan tap by remote control set during heating
thermo-off
0000 : No shift
0001 : +1 (+1.8 )
0002 : +2 (+3.6 ) to 0010 : +10 (+18 )
(Up to +6 recommended)
0000 : Provided
0001 : not provided (Automatic selection from connect-
ed outdoor unit
0000 : Standard (1 FS unit : 1 indoor unit)
0001 : Multiple unis connected ( 1 FS unit : Multiple
indoor units)
0000 : heat pump
0001 : Cooling only (no display of [AUTO] [HEAT])
0029 : Vertical air handling unit
0001: No.1 unit to 0030: No.30 unit
0001 : No.1 unit to 0064 : No.64 unit
0000 : Individual
0001 : Header unit of group
0002 : Follower unit of group
0000 : None
0001 : Restart
0000 : Usual
0001: Leaving-ON prevention control
0002 : Fire alarm input
0000 : Unavailable
0001 : Available
0000 : Body TA sensor
0001 : Remote control sensor
0000 : ̊ C ,
0001 : ̊ F
0000 : Available (Can be performed)
0001 : Unavailable (Cannot be performed)
0000 : Unavailable
0002 : Available
0000 : Heating
0001 : Cooling
0000 : Operation stop
0001 : Release signal received
0000 : Prevention control of cold air discharge "enable"
0001 : Prevention control of cold air discharge without
"Fan off" zone
0002 : Work in remote control setting fan speed.
(prevention control of cold air discharge
"disable")
Page 37 of 60
(Half of standard time)
At shipment
0000 : None
0000 : Standard
0099 : Unfixed
0000 : No priority
0001 : L tap
0002 : +2
(+3.6 )
0001 : Not provid-
ed
0000 : Standard
0000 : Heat pump
0029
0099 : Unfixed
0099 : Unfixed
0099 : Unfixed
0001 : Restart
0000 : Usual
(HA termi-
nal)
0000 : Unavailable
0000 : Body TA
sensor
0001 : ̊ F
0000 : Available
0000 : Unavailable
0000 : Heating
0000 : Operation
stop
0000 : Enable
MMD IOM 1.2 11-10-2020