Summary of Contents for Toshiba Carrier TCB-IFDMR01UP-UL
Page 1
1134755001-3 VRF DX COIL INTERFACE MODEL NAME Dx-coil controller TCB-IFDMR01UP-UL (Terminal block with relay) Dx-valve kit RBM-A0601UPVA-UL RBM-A1201UPVA-UL RBM-A1921UPVA-UL Design Guideline Design Guideline English Guide de Conception Français Directriz de Diseño Español 01_DG_1134755001-3_EN.indd 1 01_DG_1134755001-3_EN.indd 1 8/4/2567 BE 11:12 8/4/2567 BE 11:12...
Application types can be set and enable system to response according to the application. • TA type :(Main application target – Room temperature conditioning) The VRF Dx-coil interface(TA type) enables TA control of Toshiba Outdoor units connected to a DX COIL (with a field supplied AHU).
TF type (1 : 1 only) For example schematic of system ; Dx-coil controller Remote Outdoor unit controller Room 12:00 (Mon) °F Set temp. (Cool) Valve kit Operating conditions Ensure the “Coil on Air” temperature is within the range of the Dx-coil Design Guideline. Outdoor Air Supply Air Coil on Air...
Pipe Size • Maximum real piping length between valve kit and Dx coil is up to 16′5″ (5 m). (Unit : in (mm)) Pipe diameter DX COIL type (1) Gas pipe (2) Liquid pipe (3) Liquid pipe Outer diameter 0.6 - 1 3/8"...
Page 7
Refrigerant circuit diagram (1) Gas pipe Capillary Tube Header PMV: Pulse Valve kit Motor Valve DX COIL Strainer 16′5″ (5 m) Distributor Brazing Heat insulator (2) Liquid pipe Valve kit: 1 set DX COIL type: Normal (1) Gas pipe Valve kit Header PMV: Pulse Motor Valve...
Pipe length and height difference 6 Ton or more Less than 6 Ton Item TA type TF, DDC type Same as piping length restriction of Main pipe equivalent length outdoor unit Total piping length Furthest equivalent pipe length L (real length) 427 (394) 130 (120) Furthest equivalent pipe length from the 1st branch...
Product Configuration 6-1. Product Configuration DX coil type Normal (TA, TF, DDC type) Interlaced, Split face (TA type) Type Dx-coil controller Dx-valve kit Dx-coil controller Dx-valve kit RBM-A0601 RBM-A1201 RBM-A1921 RBM-A0601 RBM-A1201 RBM-A1921 Model name TCB-IFDMR01UP-UL TCB-IFDMR01UP-UL UPVA-UL UPVA-UL UPVA-UL number UPVA-UL UPVA-UL...
Page 11
• RBM-A0601UPVA-UL, RBM-A1201UPVA-UL, RBM-A1921UPVA-UL CANNOT combine in one refrigerant cycle system. Therfore, two or more AHU from 10 Ton and below Ton combination is available. In the other way, two or more AHU over 12 Ton combination is available. Please see examples below: 8 Ton 12 Ton 8 Ton...
6-3. Control Input / Output Details - Analog Input functions - TCB-IFDMR01UP-UL (Terminal block with relay) Shield wire MAX. 328′1″ (100 m) Locally procured 4 - 20 mA Signal (+) Input 4 - 20 mA GND (-) ✓ : Available ✕...
Page 14
TCB-IFDMR01UP-UL (Terminal block with relay) Shield wire MAX. 656′2″ (200 m) Locally procured 0 - 10 V Signal (+) Input 0 - 10 V GND (-) ✓ : Available ✕ : Prohibition Input Name Description Analogue Input Capacity Control Analogue Input to Capacity control. Analog Input 1 (DC 0 - 10 V) SW501 Bit-4(MCC-1777) OFF STEPPED response to analogue input...
Page 15
1) Capacity control 0-10 V (Overview of capacity control)* * There are possibilities of thermodynamic and/or mechanical limitation from many factors. which may affect our system’s heat pump cycle (refrigerant cycle) during operation. Hence, there is a possibility that the capacity output may be different from capacity control setting. SW501 Bit4 Cooling Mode Heating Mode...
Page 16
TCB-IFDMR01UP-UL (Terminal block with relay) Shield wire MAX. 656′2″ (200 m) Locally procured 0 - 10 V Signal (+) Input 0 - 10 V GND (-) ✓ : Available ✕ : Prohibition Input Name Description Set temperature changed • To use this control, set DN [4A9] = 1. •...
Page 17
- Digital Input functions - The specifications of Terminal DI1 to DI5 are as follows. • You can switch between voltage and non-voltage with SW701. SW701 SW701 SW701 MAX. 328′1″ (100 m) MAX. 328′1″ (100 m) Locally procured Locally procured Signal Voltage (DC12 V ±...
Page 18
✓ : Available ✕ : Prohibition Input Name Description Safety contact. • MODE 1 (Normally close, DC12 V) *When Bit1 of SW505 is OFF If this contact is open for more than 1 minute, the check code P10 is generated and the Dx-coil controller switches off automatically.
Page 19
✓ : Available ✕ : Prohibition Input Name Description External trouble Input An AHU fan operation monitor (Field supply), could be attached at this dry contact terminal (For example, the ✓ ✓ ✓ abnormality of the fan motor). A closed contact generates the check code L30. Forced thermostat OFF Input When signal input, AHU is in “thermostat-off”...
Page 20
TCB-IFDMR01UP-UL (Terminal block with relay) MAX. 328′1″ (100 m) Locally procured (Input, DC5 V) Relay coil signal ✓ : Available ✕ : Prohibition Input Name Description Operation ON/OFF Input When using with DDC, it starts by turning on this terminal. External trouble Input signal type(pulse / static) is selectable by Jumper Wire J01 on the Indoor(DX) P.C.
Page 21
✓ : Available ✕ : Prohibition Output Name Description Operating Output Displayed when the system starts operation (output with both ✓ ✓ ✓ thermostat ON / OFF) Alarm Active Digital Output During Alarm operation, Alarm Active Digital Output is active. ✓...
Page 22
TCB-IFDMR01UP-UL (Terminal block with relay) MAX. 1640′5″ (500 m) Locally procured Signal DO7 - DOE, N1 DC12 V DO7 - DOE, N1 Relay (DC12 V) ✓ : Available ✕ : Prohibition Output Name Description Thermostat On Digital Thermostat ON signal is output. It is usually the ON output at ✓...
Page 23
- Summary of Digital input / output function (MCC-1777) - Connector Connector Function Pin No. Wire collar Specification No. CN collar (WHI) (YEL) (ORN) PMV1 (BLU) (BLU) (RED) DC12 V (WHI) (YEL) (ORN) PMV2 (BLK) (BLU) (RED) DC12 V (BLU) (BRN) (RED) (RED)
Page 24
Connector Connector Function Pin No. Wire collar Specification No. CN collar (BLU) External ON/OFF input (YEL) (BLK) (WHI) Output Operating output (YEL) (RED) 12 V Alarm active Digital output (YEL) (BRN) Output FAN speed HH (RED) (YEL) Output FAN speed H (RED) (GRN) Output...
Page 25
TCB-IFDMR01UP-UL (Terminal block with relay) 12 12 12 12 12 12 14 14 14 14 14 14 11 11 11 11 11 11 Terminal block with relay Terminal Function Description Operating output Digital output DC12 V Alarm active digital output Digital output DC12 V Fan motor active digital output...
AHU / DX COIL Design 7-1. Equipment selection procedure -Selection flow chart- 1 Determination of air-conditioning load at each room. 2 Preliminary selection of AHU/FAHUs in the standard capacity no less than air-conditioning load at each room. 3 Calculate corrected capacity A of each AHU/FAHU by correcting of indoor temperature for the standard capacity of each AHU/FAHU.
The above capacity values are generated depends on each compressor operation level. NOTE TOSHIBA Selection Tool allows users to select [add] or [not add] the Capacity correction value. For more information, please check with TOSHIBA Selection Tool* or ask our authorized dealer.
7-3. Charging requirement with additional refrigerant Additional refrigerant charge amount (case of SMMS-u) This item describes the refrigerant correction amount of the Dx coil Interface system when connects with SMMS-u. For more information please refer to Engineering Databook of SMMS-u. Additional refrigerant charge amount at site = [1] + [2] + [3] + [4] [1].
7-4. How to select DX COIL Design Guideline How to select DX COIL Design Confi rm with AHU’s TA system can mix with VRF FCU [Cooling (only RBM-A0601UPVA-UL or & RBM-A1201UPVA-UL) Heating use] AHU Operating Desired mode application to [Cooling Only use] Guideline HP control by RA or or [Cooling &...
7-5. DX COIL Guideline H/P - Guideline H/P - < TA type > No. of refrigerant circuit by Dx-coil copper tube dia. and Dx-coil size (Ton) Number of Circuits Copper tube diameter 5/16″ 3/8″ 1/2″ Dx-coil capacity 0.6 Ton 0.8 Ton 1 Ton 1.25 Ton 1.5 Ton...
Page 32
< DDC type > No. of refrigerant circuit by Dx-coil copper tube dia. and Dx-coil size (Ton) Number of Circuits Copper tube diameter 5/16″ 3/8″ 1/2″ Dx-coil capacity 5 Ton 6 Ton 8 Ton 10 Ton 12 Ton 14 Ton 16 Ton 20 Ton 24 Ton...
7-7. DX COIL Guideline CO Pattern A - Guideline Cooling Only Pattern A - No. of Ref. Circuit by DX Coil Copper Tube Dia. and DX Coil Size (HP) Number of Circuits Copper tube 5/16″ 3/8″ 1/2″ Dx-coil 0.6 Ton 0.8 Ton 1 Ton 1.25 Ton...
Page 36
Std. 2470 3120 4240 4590 4940 5590 6240 7360 8480 8830 9180 9530 9880 12720 13070 13420 AHU Air flow rate Min. No restriction (cfm) Max. No restriction Min. 259 311 414 466 518 570 622 725 828 880 932 984 1036 1242 1294 1346 Dx-coil internal volume (inch³) Max.
7-8. DX COIL Guideline CO Pattern B Guideline Cooling Only Pattern B - No. of Ref. Circuit by DX Coil Copper Tube Dia. and DX Coil Size (HP) Number of Circuits Copper tube 5/16″ 3/8″ 1/2″ Dx Coil 0.6 Ton 0.8 Ton 1 Ton 1.25 Ton...
Page 38
Std. 2470 3120 4240 4590 4940 5590 6240 7360 8480 8830 9180 9530 9880 12720 13070 13420 AHU Air flow rate Min. No restriction (cfm) Max. No restriction Min. 137 192 220 247 275 330 384 725 439 880 494 984 549 659 687 714 Dx-coil internal volume (inch³) Max.
The TA, TF sensor which is combined in the Dx-coil controller must be located right position for position TOSHIBA control, not demand control. The cooling/heating demand is determined from the DDC. Following the below example picture: *1: TF sensor can only be used with SMMS-u and SHRM-u.
7-12. Dx-valve kit Installation Installation Avoid locations in direct sunlight. Standard Rating ; IPX4 Environment Insulation should be fi tted to Dx-valve kit (locally sourced). Ideally the Dx-valve kit should be contained within the AHU. If installed outside, a cover (locally sourced) should be fi...
Page 42
Wire • Connect the cable from the PMV. Match the color of the wiring of the PMV side and the controller Connections side. • For the PMV, sensor wiring, do not bundle it with the motor wiring. The wrong operation may result in. •...
Control Outline 8-1. Cautions regard with DDC’s programing (1) Operation Start - Capacity control signal(analogue input voltage) should be output after the AHU’s fan operating. Then, recommend to keep more than 50%(Heating; 40%) Capacity control signal during 5 mins. - To protect the compressor, for 5 mins after operation start the compressor will continue to operate even if receives “Zero”...
8-2. Protection Function Summary • Protection Controls varies by Outdoor unit, please see appropriate Outdoor unit service manual for full details (Below “Protection Function Summary” is according to SMMS-u.) Function Summary Freeze prevention control In Cooling Mode prevents low DX-COIL temperatures by controlling compressor speed (Low temperature release) (based on TC1/TC2/TCJ sensor temperature).
Page 45
Function Summary IPDU control (1) Current, power release value control (IPDU = The purpose of this control is to prevent high pressure rise and overheating of electric parts Inverter P.C. Board by reducing the compressor speed when the maximum current and maximum power value for compressor) set for each model are exceeded.
Cable specifications Communication line (Uv(U1), Uv(U2)) Uv: Control wiring between Dx-coil controller and outdoor unit Wiring 2-core, non-polarity Type Shield wire Size / Lengh AWG 18 to AWG 16 / up to 3280′10″ (1000 m) Remote controller wiring (A, B) Wiring 2-core, non-polarity Size...
Modbus setting method Modbus communication is available on this model. Follow the procedure below to set. CAUTION Use insulation type for Modbus devices to be connected. If it is not an insulation type, it may affect the device due to noise, etc. 1.
Page 48
2. Function codes Function code Sub function code Function name 0×03 None Read holding register 0×04 None Read Input register 0×06 None White single holding register 0×08 0×00, 01, 02, 04, 0A, 0B, 0C, 0D, 0E, 0F, 11, 12, 14 Diagnostics 0×0B None...
Page 49
Register address Read / Write Data Byte Data Definition and remarks Input Register 0 : STOP 30001 Operation / stop setting 1 : OPERATE 1 : HEATING MODE 30002 Operation mode setting 2 : COOLING MODE 3 : DRY MODE 30003 Set temperature setting 2 10 times values...
Page 50
Data Definition and remarks Register address Read / Write Data Byte Input Register 30073 ~ 30078 Reserved Under restriction of compressor speed due 0 : OFF 30079 to heat sink overheating in outdoor unit(s) 1 : ON 0 : OFF 30080 Cooling / heating start control output 1 : ON...
Function code (DN code) ▼ Function CODE No. (DN code) table (setting by wired remote controller) Item Description Default (at shipment) Filter display delay timer 0000: None 0000: None 0001: 150H 0002: 2500H 0003: 5000H 0004: 10000H Dirty state of filter 0000: Standard 0000: Standard 0001: High degree of dirt (Half of standard time)
Compatibility with Remote Controller, BMS, Open network system TU2C-LINK models ✓ : Available ✕ : Prohibition Model Name and Model Name and Appliance name Appliance name appearance appearance Remote Controller Open network and analog interface RBC-AWSU52-UL BMS-IFBN1281U-UL BACnet IP ✓ ✕...
Page 56
TCC-LINK models ✓ : Available ✕ : Prohibition Model Name and Model Name and Appliance name Appliance name appearance appearance Remote Controller Open network and analog interface RBC-ATM32UL TCB-IFLN642TLUL ✓ ✓ ✓ LON Interface ✓ ✕ ✕ RBC-AMS41UL BMS-IFBN640TLUL ✓ ✓...
Check Codes Common Check Codes (Note1 : DDC(0-10 V) type P.C. Board is classifi ed as a Remote controller) (Note2 : Regarding outdoor units, refer to their own service manuals) - E01 : No master remote controller, faulty remote controller communication The header remote controller has not been set.
- Toshiba Carrier shall not be liable for any damage to the entire system or the AHU main body caused by connected AHU with wrong specification or wrong usage of AHU.