Bus combined smoke and heat detector

Advertisement

The JA-110ST Bus combined smoke and heat detector
When connecting the module to the bus,
always switch the system's power off.
4. Proceed according to the control panel installation manual.
Standard procedure:
a. When the device is powered, the yellow LED starts flashing
repeatedly to indicate that the module has not been enrolled
into the system.
Go to the F-Link program, select the required position in the
b.
Devices tab and enter the Enrollment mode by clicking on
the Enroll button.
c. Click on "Scan/add new BUS devices", select the detector from
the list and double-click on it to confirm your selection.
The yellow LED light will stop flashing.
5. Insert the detector into the plastic base. It can only be inserted in
the position marked with arrows (4) on both plastic parts. Close the
detector by turning it clockwise (2). When the detector is fully
secured to the base, a control LED lights up (3), which indicates an
automatic detector test. During this period of time, the detector
won't detect anything. The test ends when the LED shuts down (3)
and the detector becomes fully operational. A possible detector
fault may be indicated. See the Fault indication chapter.
Notes:
In order to facilitate identification when enrolling the detector
in F-Link, we recommend removing the sticker with a serial code
before inserting the detector into the plastic base. Paste it onto
a piece of paper and write down the location of the detector.
The detector can be also enrolled by entering the Enrollment
mode and inserting the detector into the plastic base.
Alternatively the detector can be enrolled by entering its serial
number (5) in the F-Link program. All numbers stated under the bar
code shall be entered (1400-00-0000-0001).
Detector settings
Go to the Devices window in the F-Link program. When you are at
the detector's position, use the Internal settings option to open
a dialog window where you can set:
Reaction: it's possible to choose whether the detector will react
to smoke, heat, smoke or heat or smoke and heat at the same
time.
Fire alarm
Optical detector: When smoke enters the detector, an alarm
is triggered, and it is signaled with a rapidly flashing red LED light
(approx. 8 times per second). The indication lasts until the detector's
detection chamber is ventilated.
Heat detector: When the temperature rises above limit, an alarm is
triggered, and it is signaled with a rapidly flashing red LED (approx.
8 times per second). The indication lasts until the temperature drops
(e.g. when the room is ventilated).
Alarm memory: If enabled, LED alarm indication continues to flash
slowly (approx. twice per second) for further 24 hours after the alarm
stops. The indication can be terminated by unsetting the section in
which the detector is installed.
Tamper alarm: When the detector cover is opened, the detector
sends a tamper signal, unless the control panel is in Service mode.
Detector testing and maintenance
The functionality of the optical part of the detector can be tested with
a test spray. The functionality of the heat part can be tested with
a hairdryer. If the detector is configured to be triggered by both
conditions, it's necessary to conduct both spray and hairdryer tests at
the same time. The test should be carried out once every 30 days. The
detector's cover should be cleaned regularly from cobwebs and dust.
Test button: Pressing the test button will start the automatic
detector test. A result of this test is indicated by displaying a green
or red circle. The green circle means that the detector works
correctly. However the red circle indicates a fault of the detector. In
this case, repeat the test. If the fault appears repeatedly then it is
necessary to send the detector to the service for repair.
Warning: never test the detector with fire inside the building
The JA-110ST Bus combined smoke and heat detector
Fault indication
The detector checks its functionality. When a fault is discovered, the
LED indicator immediately flashes 3 times and then briefly 3 times
every 30 seconds. The automatic test indicates a fault the same way.
See the Installation chapter
The error found may be caused by a fault of the detection chamber,
the temperature of the environment being out of the operating
temperature range or other faults of the detector.
An operating temperature range fault will disappear the moment the
temperature of the environment turns back to normal.
Other faults found are indicated as a fault even after their cause has
gone. The fault indication can be stopped by the functionality test. The
basic functionality test is triggered by opening the detector cover (fig 6-
1), removing the lower plastic part and putting it back (fig 6-2). If this
test results in a fault again, send the detector to the repair service.
WARNING! The control panel must be switched to Service mode
otherwise a Tamper alarm will be triggered.
Technical specifications
Power
Current consumption in standby mode
Current consumption for cable selection
Dimensions
Weight
Smoke detection
Smoke detector sensitivity
Heat detection
Alarm temperature
Operating temperature range
Complies with
15 1293-CPR-0507
JABLOTRON ALARMS a.s. hereby declares that the JA-110ST is in a compliance
with the relevant Union harmonisation legislation: Directives No: 2014/30/EU,
2011/65/EU. The original of the conformity assessment can be found
at www.jablotron.com - Section Downloads.
Note: Although this product does not contain any harmful
materials we suggest you return the product to the dealer or directly
to the producer after use.
2 / 2
from control panel digital bus 12 V (9...15 V)
diameter 126 mm, height 50 mm
optical light scattering
m = 0.11 - 0.13 dB/m pursuant to EN 54-7
class A2 according to EN 54-5
+60 °C to +70 °C
-10 °C to +80 °C
EN 54-5, EN 54-7
EN 50130-4, EN 55022
MLW51612
5 mA
10 mA
143 g