Transmission Data - M-system R1D-GH2 Instruction Manual

Thermocouple & dc input module

Advertisement

INPUT RANGE SELECTING
Select switches to match the input signal according to the table below.
SW411
SW401 SW308 SW307 SW306
1
O
2
N
3
4
5
6
7
8
SW408 SW407 SW406
INPUT
Thermocouple
Voltage input, 0.8V or less
Voltage input, above 0.8V (*)
(*) Factory setting unless specific input types and ranges are specified when ordering

TRANSMISSION DATA

■ INPUT: Thermocouple or DC input*, 16 points
Input resistance: 300 kΩ
Thermocouple types: PR, K, E, J, T, B, R, S, C, N, U, L, P
MEASURING RANGE
±20V, ±5V, ±1V
±0.8V, ±0.2V, ±50mV, ±10mV
Sampling rate: 150 millisec./16 points
* Common negative for DC input
SWITCHES
SW301 – SW308 (ch 1 – ch 8)
SW401 – SW408 (ch 9 – ch 16)
SW311 (ch 1 – ch 8)
SW411 (ch 9 – ch 16)
SW301 – SW308 (ch 1 – ch 8)
SW401 – SW408 (ch 9 – ch 16)
SW311 (ch 1 – ch 8)
SW411 (ch 9 – ch 16)
SW301 – SW308 (ch 1 – ch 8)
SW401 – SW408 (ch 9 – ch 16)
SW311 (ch 1 – ch 8)
SW411 (ch 9 – ch 16)
NOTES
Atten. SW ON (3)
Atten. SW OFF (1)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
SW311 SW305 SW304 SW303 SW302
1
O
2
N
3
4
5
6
7
8
SW405 SW404 SW403 SW402
SETTING
Set to position "1"
OFF
Set to position "1"
ON
Set to position "3"
ON
■ ANALOG INPUT
A/D conversion output: 16-bit signed binary (negative
range represented by 2's complements)
Engineering unit value is converted into A/D conversion
data as shown in the table below.
INPUT TYPE & RANGE
±20V
±5V
±1V
±0.8V
±0.2V
±50mV
±10mV
Thermocouples
In order to change input type and range after shipment, the
R1X configurator software (model: R1CON) is required.
R1D-GH2
SW301
NOTES
Attenuation OFF
Attenuation OFF
Attenuation ON
A/D DATA (decimal)
±20000
±5000
±10000
±8000
±20000
±5000
±10000
Temperature × 10
EM-5958 Rev.7 P. 4 / 5