CAUTION
The unit body should align perfectly with the hole. Ensure that the
unit and the hole are the same size before proceding further.
2. Drill 4 holes 50 mm deep at the ceiling hook positions in the internal
ceiling. Ensure to hold the drill at a 90° angle to the ceiling.
3. Using a hammer, insert the ceiling hooks into the pre-drilled holes.
Secure the bolt using the included washers and nuts.
4. Install the four suspension bolts (See Fig. 6).
Fig. 6.
5. Mount the indoor unit. You will need two people to lift and secure it.
Insert suspension bolts into the unit's hanging holes. Fasten them
using the included washers and nuts (See Fig. 7).
Climate 5000 SCI – 6720887405 (2018/04)
> 1000mm
> 1000mm
> 1000mm
Fig. 7.
NOTE:
The bottom of the unit should be 10 - 18 mm higher than the ceiling
board. Generally, L (indicated in Fig. 8) should be half the length of the
suspension bolt or long enough to prevent the nuts from coming off.
Wall
L
10 - 18 mm
Ceiling board
Fig. 8.
CAUTION
Ensure that the unit is completely level. Improper installation can
cause the drain pipe to back up into the unit or water leakage.
NOTE:
Ensure that the indoor unit is level. The unit is equipped with a built-in
drain pump and float switch. If the unit is tilted against the direction
of condensate flow (the drainpipe side is raised), the float switch may
malfunction and cause water to leak.
Water level
Fig. 9.
Indoor Unit Installation
Main body