Indoor Unit Installation; Indoor Unit Parts; Indoor Unit Installation Instructions - Bosch Climate 5000 SCI Installation Manual

Cassette-type air conditioner
Hide thumbs Also See for Climate 5000 SCI:
Table of Contents

Advertisement

4

Indoor Unit Installation

4.1

Indoor Unit Parts

Drain pump
(within indoor unit)
Drain pipe
Louver
Display panel
Refrigerant pipe
Fig. 1.
Safety Precautions
WARNING
• Securely install the indoor unit on a structure that can sustain its
weight. If the structure is too weak, the unit may fall and cause
personal injury, unit and property damage.
• Install the indoor unit at a height of more than 2.5 m above the floor.
• DO NOT install the indoor unit in a bathroom or laundry room, as
excessive moisture can short the unit and corrode the wiring.
CAUTION
• Install the indoor and outdoor units, cables, and wires at least 1 m
from televisions and radios to prevent static or image distortion.
Depending on the appliances, a 1 m distance may not be sufficient.
• If the indoor unit is installed on metal, it must be electrically
grounded.
Climate 5000 SCI – 6720887405 (2018/04)
Air outlet
Air inlet
Front grille
4.2

Indoor Unit Installation Instructions

NOTE:
Panel installation should be done after piping and wiring.
Step 1: Select installation location
The indoor unit should be installed in a location that meets the following
requirements:
f The unit is at least 1 m from the nearest wall.
f There is enough room for installation and maintenance.
f There is enough room for the connecting pipe and drainpipe.
f The ceiling is horizontal and its structure can sustain the weight of
the indoor unit.
f The air inlet and outlet are not impeded.
f The airflow can fill the entire room.
f There is no direct radiation from heaters.
CAUTION
DO NOT install the unit in the following locations:
In areas with oil drilling or fracking
In coastal areas with high salt content in the air In areas with caustic
gases in the air, such as near hot springs
In areas with power fluctuations, such as factories
In enclosed spaces, such as cabinets
In kitchens that use natural gas
In areas with strong electromagnetic waves
In areas where store flammable materials or gas are stored
In rooms with high humidity, such as bathrooms or laundry rooms
RECOMMENDED DISTANCES BETWEEN THE INDOOR UNIT AND
THE CEILING
The distance between the mounted indoor unit and the internal ceiling
should meet the following specifications. (See Fig. 2)
Indoor Unit Installation
7