Configuration; Dip Switches (Aq101, Aq101D, Aq110P); Aq101, Aq101D - Siemens Arcteq AQ101 Instruction Manual

Table of Contents

Advertisement

Instruction manual AQ101, AQ101D, AQ110P, AQ01
2
C
ONFIGURATION
2.1
DIP
SWITCHES
Functionality such as tripping logic is configured using dipswitch settings. Tripping
may be selected based on arc light only or arc light and current thresholds.
Scheme selection is made with dip switches by calculating the sum
of weight factors
2.1.1

AQ101, AQ101D

2.1.1.1
Scheme 0
SW 1
no
OFF
ON
8
7
6
5
4
3
2
1
Table 2-1: AQ101, AQ101D scheme 0 DIP switches definition.
*) Circuit breaker failure protection function is not included in the scheme 0.
(AQ101, AQ101D, AQ110P)
Text
8
L> / L> + I>
Tripping with light only criterion.
7
S1: L> / L> + I>
Sensor 1 tripping with light only
6
Latch: On / Off
5
100 / 150 ms*
Circuit breaker failure protection
4
3
Scheme
Select
2
1
Function at ON position
criterion.
Output relays latched.
operating time 100 ms.
Weight factor 0
Weight factor 0
Weight factor 0
Weight factor 0
Function at OFF position
Tripping with light and current
criterion.
Sensor 1 tripping with light and
current criterion.
Output relays not latched.
Circuit breaker failure protection
operating time 150 ms.
Weight factor 8
Weight factor 4
Weight factor 2
Weight factor 1
)
12 (48